Table 8-18. feeder_4 function block logic -37 – Basler Electric BE1-851 User Manual

Page 193

Advertising
background image

Contingency Operation - Backup Protection for Feeder Breaker Failure

OUT5 is configured as the breaker failure trip output. OUT5 can be wired to trip the bus breaker or a

lockout relay. The breaker failure pickup (BFPU) output trips the feeder breaker directly via output 1 to

provide a breaker re-trip signal for added security.
Initiation of the BF function block by external relays is provided by IN3. The 150T function blocks provide

fault detector supervision of the external initiate signal. The logic uses the pickup outputs of the function

blocks. In this application, the time delay settings should be set to maximum so that they do not time out

and trip targets. If the external BFI signal from protective relays such as 81 or 87T where fault detector

supervision is not desired, the BESTlogic expression for VO12 which is the BFI logic expression in this

logic scheme, can be modified.
The BF function block is also initiated by a protective trip. This function block has an independent fast

drop out phase and ground current detector that detects a breaker opening and stops timing. An open

breaker is detected when the current drops below 10% of nominal. Setting the time delay at zero disables

the BF function block. This permits the traditional radial system backup scheme of coordinated relays

tripping different breakers.
Feeder_4 logic stops the block signal to allow the bus relay to trip the bus breaker through its 50T

elements if a direct trip is not desired. This provides clearing of the fault on the circuit with the failed

breaker in feeder relay breaker failure time (or bus relay 50T time; whichever is greater) instead of the

bus relay 51 time but is limited by the sensitivity constraints of the bus relay.

Contingency Operation - Backup Protection for Feeder Relay Out-of-Service

Primary protection for relay failure is provided by redundant relays applied to the feeder.

Table 8-17. Feeder_4 Contact Sensing Input Logic

Input

Purpose

Name Label

State Labels

Energized

De-Energized

IN1

52b Breaker Status.

BREAKER

OPEN

CLOSED

IN2

Enable recloser when IN2 is energized. RCL_ENABLE

ENABLED

DISABLD

IN3

Enable neutral and negative-sequence,

50 and 51 protection when IN3 is

energized.

N&Q_ENABLE

ENABLED

DISABLD

IN4

Put the relay in test mode so that

reclosing and breaker failure are

disabled when IN4 is de-energized.

TESTDISABL

NORMAL

TSTMODE

Table 8-18. Feeder_4 Function Block Logic

Function

Purpose

BESTlogic

Expression

Mode

Setting

50TP

Used for instantaneous phase overcurrent protection.

Block when recloser sequence controlled blocking

output is TRUE.

79SCB

1 (enabled)

50TN

Used for instantaneous neutral overcurrent protection.

Block when recloser sequence controlled blocking

output is TRUE or when disabled by Virtual Switch

243.

79SCB+243

1 (enabled)

9289900990 Rev R

BE1-851 Application

8-37