Pickup

Pickup expressions are used by the fault reporting function to time-stamp the fault summary record, time

the length of the fault from pickup to dropout (fault clearing time), and to control the recording of

oscillographic data. The pickup expression is used to flash, on and off, the Trip LED on the HMI. The Trip

LED will continue to flash on and off as long as the pickup expression is true and the trip expression is not

true. A pickup expression is also used by the setting group selection function to prevent a setting group

change during a fault.

Logic

LOGIC trigger expressions allow the fault reporting function to be triggered even though the relay is not

picked up. A logic trigger expression provides an input to the fault reporting function much as the pickup

expression does. This logic expression is not used by the setting group selection or the HMI.

Fault Reporting Trigger Settings

Fault reporting trigger settings are made from the BESTlogic Function Element screen in BESTCOMS.

Figure 6-12 illustrates the BESTCOMS screen used to select BESTlogic settings for the Fault Recording

function. To open the BESTlogic Function Element Screen for Fault Recording, select Reporting and

Alarms from the Screens pull-down menu. Select the Fault Recording tab. Then select the Logic button in

the upper left hand corner of the screen. Alternately, settings may be made using SG-TRIGGER ASCII

command.
To connect the function’s inputs, select the button for the corresponding input in the BESTlogic Function

Element screen. The BESTlogic Expression Builder screen will open. Select the expression type to be

used. Select the BESTlogic variable or series of variables to be connected to the input. Select Save when

finished to return to the BESTlogic Function Element screen. For details on the BESTlogic Expression

Builder, See Section 7, BESTlogic Programmable Logic. Select Done when the settings have been

completely edited. Trigger settings for fault reports are made using the SG-TRIGGER (settings-general,

trigger) command.

Figure 6-12. BESTlogic Function Element Screen, Fault Recording


Table 6-10 provides the Fault Recording Trigger settings.

6-20

BE1-851 Reporting and Alarms

9289900990 Rev R