Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 2

Drive Start Up

Configure the Speed Feedback Parameters

1.

Access the “Speed Feedback” group.

2.

Configure the following parameters:

Note: If an encoder or tachometer is used, see Drive Reference and
Feedback Scaling
on page

265

for instructions on associated parameter

settings.

❏ Par 414 [Fdbk Device Type] - Select the source for motor velocity

feedback:

1 “Encoder”

2 “DC Tach”

3 “Armature” (default)

4 “Resolver”

If operating the drive in field weakening mode, Par 414 [Fdbk
Device Type] must be set to 1 “Encoder”, 2 “DC Tach”, or 4
“Resolver.”

❏ Par 457 [Spd Fdbk Control] - If you are using an encoder,

tachometer, or resolver set this parameter to 1 “Enabled” to activate
speed feedback control.

❏ If the speed feedback source is an analog tachometer, set the fine

scaling value in Par 562 [Anlg Tach Gain]. This value is used to scale
the analog tachometer feedback signal after it has been conditioned
by the drive hardware.

❏ If the speed feedback source is a digital encoder, complete the

following steps:

a.

Enter the pulses per revolution from the encoder nameplate in
Par 169 [Encoder PPR]. See Speed Feedback on page

269

for

more information on setting the value of this parameter.

b. Set Par 652 [Encoder Err Chk] to 1 “Enabled” to activate

monitoring of the digital encoder signals (verifies the presence
of the A, B, A-, B-, or Z channel signals).

Par 457 [Spd Fdbk Control] must be set to 1 “Enabled” for
encoder monitoring to occur.

Switch S20 must be set correctly to prevent encoder faults. See

Table 26

on page

73

.

ATTENTION: The drive can overspeed if DIP switch S4 is set
incorrectly, or the tach is wired incorrectly. Failure to observe this
precaution could result in damage to the drive or process equipment.
See

Table 50

on page

74

.