Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 166

Advertising
background image

166

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 3

Programming and Parameters

UTILIT

Y

Diagno

st

ic

s

382

[Drive Status 2]

Present operating condition of the drive.
Bit 0 “Ready” - When set (= “1”), the drive is ready
Bit 1 “Active” - When set, the drive is active
Bit 2 “Running” - When set, the drive is running
Bit 3 “Jogging” - When set, the drive is being jogged
Bit 4 “Stopping” - When set, the drive is stopping
Bit 6 “Auto Tuning” - When set, the drive is auto tuning
Bit 7 “Forced Spd” - When set, the drive is in forced speed mode
Bit 8 “Speed Mode” - When set, the drive is in speed mode
Bit 9 “Torque Mode” - When set, the drive is in torque mode
Bit 10 “SpdRegPosLim” - When set, the Speed Regulator PI positive limit is active
Bit 11 “SpdRegNegLim” - When set, the Speed Regulator PI negative limit is active
Bit 12 “ArmAlphaTest” - When set, the Armature Alpha test is active
Bit 13 “FldAlphaTest” - When set, the Field Alpha test is active
Notes: Added bits 7…13 for firmware version 3.001. See Torque Mode Selection Status Bits on page

299

for

more information.

Read Only

393

[Speed Threshold]

Indicates if the drive is above or below the threshold speed specified in parameters
101 [Speed Thresh Pos] (clockwise rotation) and 102 [Speed Thresh Neg] (counter-
clockwise rotation).
“0 Above Thresh” = The speed has exceeded the set speed threshold.
“1 Below Thresh” = The speed has not exceeded the set speed threshold.
Notes: This parameter can be assigned to a digital output. See Speed Threshold
Indicators o
n page

291

for more information.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

101,
102,
103

394

[At Speed]

Indicates whether or not the current speed of the drive corresponds to the speed
reference (specified in Par 118 [Speed Reg In]) before the speed regulator and the
ramp reference (if enabled) are applied. The speed above and below the speed
reference at which [At Speed] will indicate “1 Equal” is set in Par 104 [At Speed
Error].
“0 Not Equal” - The drive is not working at the set speed reference.
“1 Equal” - The drive is working at the set speed reference.
Notes: This parameter can be assigned to a digital output. It also corresponds to
the “At Speed” indication on the Status Line of the HIM. See Speed Threshold
Indicators o
n page

291

for more information.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

104,
105

395

[At Zero Speed]

Indicates whether or not the actual speed of the motor is below the zero speed
threshold as specified in Par 107 [Speed Zero Level].
“0 Equal” - The actual speed is below the value of Par 107 [Speed Zero Level]

and Par 108 [Speed Zero Delay] has timed out.

“1 Not Equal” - The actual speed is above the value of Par 107 [Speed Zero

Level].

Notes: This parameter can be assigned to a digital output. See Speed Threshold
Indicators o
n page

291

for more information.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

107,
108

396

[MOP Inc Active]

Indicates whether or not the drive is accelerating using the preselected ramp.
0 “No Accel” = the drive is not accelerating using a preselected ramp
1 “Accel” = the drive is accelerating using a preselected ramp

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

Options

Res

er

ved

Res

er

ved

Fl

dA

lp

ha

Te

st

Ar

m

Al

ph

aT

es

t

SpdRegN

egLim

SpdRegP

osLim

To

rq

ue

Mode

Speed

Mode

Fo

rc

ed

S

pd

Auto

T

un

in

g

Cu

rr Limit

Stop

pi

ng

Jo

gg

ing

Ru

nni

ng

Ac

tiv

e

Ready

Default

x

x

0

0

0

0

0

0

0

0

0

0

0

0

0

1

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

A

A

Advertising