Clearing alarms, Alarm descriptions, Clearing alarms alarm descriptions – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 206: D/or alarm, Descriptions on

Advertising
background image

206

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 4

Troubleshooting

Clearing Alarms

Alarms are automatically cleared when the condition that caused the alarm is no
longer present.

Alarm Descriptions

The status of the alarms can be viewed in

1380

[Drive Alarm 1].

Table 41 - Alarm Descriptions and Actions

Alarm

Type

Description

Arm Overvoltage 1

There is a possible overvoltage on the armature circuit or Par

175

[Rated Motor Volt] is set too

low for the application. See the “Arm Overvoltage” fault description on

page 202

for more

information.

Auxiliary Input

1

An auxiliary input interlock is open or a voltage (+15 - 30 V) or reference signal is missing for
the digital input set to 14 “Aux Fault”. See the “Auxiliary Input” fault description on

page 202

for more information.

BipolarCflct

2

Par

1322

[Direction Mode] is set to “Bipolar” or “Reverse Dis” and one or more of the

following digital input functions is configured: “Fwd/Reverse,” “Run Forward,” “Run
Reverse,” “Jog Forward” or “Jog Reverse.”

CntactrCflct

2

Contactor input functions are in conflict:
When Par

1391

[ContactorControl] is set to “None”, both relay outputs (Pars

1392

[Relay

Out 1 Sel] and

629

[Relay Out 2 Sel] and all digital inputs ([Digital Inx Sel]) cannot be set

to “Contactor” or “ContactorDB”.

With [ContactorControl] set to “AC Cntcr” or “DC Cntcr”, one relay output and one digital

input must be set to “Contactor”. No relay or digital output can be defined as
“ContactorDB”.

With [ContactorControl] set to “AC Cntcr+DB” or “DC Cntcr+DB”, both relay outputs and

one digital input must be set to “Contactor”, “ContactorDB” and “Contactor”, respectively.

Because any relay output can be configured as contactor or DB control and any digital input
as contactor status, care must be taken to correctly wire the terminal blocks to match the
parameter selections.

DigInCflctA

2

Digital input functions are in conflict. Combinations marked with a “ ” will cause an alarm.

DigInCflctB

2

One of the following digital input conflicts exists:
A digital Start input has been configured without a Stop input
None of the digital inputs are configured for “Enable”
Other digital input functions are in conflict. Combinations that conflict are marked with a

“ ” and will cause an alarm.

Acc2/Dec2 Accel 2 Decel 2 Jog 1/2 Jog Fwd

Jog Rev

Fwd/Rev

Acc2/Dec2

Accel 2

Decel 2

Jog 1/2

Jog Fwd

Jog Rev

Fwd/Rev

Start

Stop-

CF

Run Run Fwd Run Rev

Jog

1/2 Jog Fwd Jog Rev

Fwd/

Rev

Start

Stop-CF

Run

Run Fwd

Run Rev

Jog 1/2

Jog Fwd

Jog Rev

Fwd/Rev