Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

229

Supplemental Drive Information

Appendix A

Table 65 - Recommended Leg Fuses - 690V AC Input Frame C Drives

Table 66 - Recommended Leg Fuses - 690V AC Input Frame D Drives

Figure 68 - Frame C Regenerative Drive - Leg Fuse Location

Fram

e

Drive
Current
Rating
Code

DC
Amps

AC
Line
Amps

Qty Bussmann

Ferraz Shawmut (Gould Shawmut)

SIBA

Square Body - Flush End Contact

C 452

452

369

6

170M5394 + switch 170H0069

12,5 URD 72 TTF 0500 + switch MS 3V 1-5 BS

20 771 32.500 + switch 28 001 04

565

565

461

6

12,5 URD 72 TTF 0630 + switch MS 3V 1-5 BS

20 771 32.630 + switch 28 001 04

Fram

e

Drive
Current
Rating
Code

DC
Amps

AC Line
Amps

Qty

Bussmann

Ferraz Shawmut (Gould Shawmut)

SIBA

Square Body - DIN 43653 Stud-Mount

D

678

678

553

6

170M6244 + switch 170H0069

G300570 + switch MS 3V 1-5 UR

20 735 32.630 + switch 28 001 04

791

791

645

6

170M6246 + switch 170H0069

J300572 + switch MS 3V 1-5 UR

20 735 32.800 + switch 28 001 04

904

904

738

6

170M6247 + switch 170H0069

K300573 + switch MS 3V 1-5 UR

20 735 32.900 + switch 28 001 04

1K0

1017

830

6

170M6248 + switch 170H0069

L300574 + switch MS 3V 1-5 UR

20 735 32.1000 + switch 28 001 04

1K1

1130

922

12

170M6244 + switch 170H0069

G300570 + switch MS 3V 1-5 UR

20 735 32.630 + switch 28 001 04

1K2

1243

1014

12

170M6244 + switch 170H0069

G300570 + switch MS 3V 1-5 UR

20 735 32.630 + switch 28 001 04

1K4

1413

1153

12

170M6245 + switch 170H0069

H300571 + switch MS 3V 1-5 UR

20 735 32.700 + switch 28 001 04

1K5

1582

1291

12

170M6246 + switch 170H0069

J300572 + switch MS 3V 1-5 UR

20 735 32.800 + switch 28 001 04

Note: Drive shown with front covers removed and control board EMI shield lowered.