Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 245

Advertising
background image

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

245

Supplemental Drive Information

Appendix A

Alternate Dynamic Brake
Resistor Kits and DC Output
Contactors

The following alternate dynamic brake resistor kits and/or DC output contactors
may be used with the corresponding PowerFlex DC drives but must be sourced
separately from the drive.

Table 81 - 230V AC Input Drives

Table 82 - 460V AC Input Drives

Fr

am

e

Drive
Current
Rating
Code

DC
Amps

AC
Line
Amps

Hp

Dynamic Brake Resistor
Kit Cat. No.

Armature
Voltage
(Volts)

DB Resistor
Size (ohms)

DB
Resistor
Size
(Watts)

Brake
Amps
Required

DC Loop Contactor Cat. No.

(2)

DC Contactor
Crimp Lugs Cat.
No.

(3)

Drive w/No Dynamic Brake

Drive w Dynamic Brake

B

360

360

294

100

1370-DBL76

240

1.4

290

171.43

ABB_EHDB360C2P-1L2S

ABB_EHDB360C-1L22SS

(4)

434

434

355

125

CUTLER-HAMMER_G3AP50
(Qty 4 - two in series, two in
parallel)

240

0.5

1458

651

ABB_EHDB520C2P-1L2S

ABB_EHDB520C-1L22SS

C

521

521

426

150

HUBBELL_Y139W322GB

240

0.322

6221

781

700

700

572

200

(1)

240

ABB_EHDB800C2P-1L2S

ABB_EHDB800C-1L22SS

D

875

875

715

250

240

ABB_EHDB960C2P-1L2S

ABB_EHDB960C-1L22SS

1K0

1050

858

300

240

SIEMENS-MFG_14-193-101-58-
2 (Qty 2)

SIEMENS-MFG_14-193-101-58-2 (Qty
1)

(1) No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally.

(2)

Coil voltage = 115V AC, 50/60Hz.

(3)

See DC Contactor Crimp Lug Kit Specifications on page

244

for more information.

(4) Wire and Lug size dependant on enclosure dimensions and local codes.

Fram

e

Drive
Current
Rating
Code

DC
Amps

AC Line
Amps

Hp

Dynamic Brake Resistor Kit
Cat. No.

Armature
Voltage
(Volts)

DB Resistor
Size (ohms)

DB
Resistor
Size
(Watts)

Brake Amps
Required

DC Loop Contactor Cat. No.

(2)

DC Contactor
Crimp Lugs
Cat. No.

(3)

Drive w/No Dynamic Brake

Drive w Dynamic Brake

B 330

330

269.6

200

1370-DBH79

500

0.7

280

714.29

ABB_EHDB360C2P-1L2S

ABB_EHDB360C-1L22SS

(4)

412

412

336.6

250

HUBBELL_Y95W808GB

500

0.808

7292

ABB_EHDB520C2P-1L2S

ABB_EHDB520C-1L22SS

C 495

495

404.4

300

HUBBELL_Y101W595GB

500

0.595

6069

ABB_EHDB520C2P-1L2S

ABB_EHDB520C-1L22SS

667

667

544.9

400

HUBBELL_Y109W542GB

500

0.542

6439

ABB_EHDB800C2P-1L2S

ABB_EHDB800C-1L22SS

D 800

830

678.1

500

(1)

500

0.463

6338

ABB_EHDB960C2P-1L2S

ABB_EHDB960C-1L22SS

960

996

813.7

600

500

0.322

6221

SIEMENS-MFG_14-193-101-58-2 (Qty
2)

SIEMENS-MFG_14-193-101-58-2
(Qty 1)

1K1

1162

949.4

700

500

0.322

6221

SIEMENS-MFG_14-193-101-58-2 (Qty
2)

SIEMENS-MFG_14-193-101-58-2
(Qty 1)

1K3

1328

1085.0

800

500

0.255

5718

CUTLER-HAMMER_6702ED636-2 (Qty
2)

CUTLER-HAMMER_6702ED636-2 (Qty
1)

1K4

1494

1220.6

900

500

0.255

5718

CUTLER-HAMMER_6702ED636-2 (Qty
2)

CUTLER-HAMMER_6702ED636-2 (Qty
1)

(1) No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally.
(2) Coil voltage = 115V AC, 50/60Hz.
(3) See DC Contactor Crimp Lug Kit Specifications on page

244

for more information.

(4) Wire and Lug size dependant on enclosure dimensions and local codes.

Advertising