Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 140

Advertising
background image

140

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 3

Programming and Parameters

SPEED C

O

MMAND

Spe

ed Regula

to

r

96

[Spd Reg Neg Lim]

Negative Speed Regulator output limit. When this limit is active the negative
integrator portion of the PI regulator is held to prevent windup.
Note: This parameter was added for firmware version 3.001.

Default:

Min/Max:
Units:

–200.00

–/+250.00
%

Real

95

99

[Spd Reg Kp Outpt]

Displays the active proportional coefficient of the speed regulator as a
percentage of the value defined in Par 93 [Spd Reg Kp Base].

Default:

Min/Max:
Units:

Read Only

0.00 / 100.00
%

Real

87,
93

100

[Spd Reg Ki Outpt]

Displays the active integral coefficient of the speed regulator as a percentage
of the value defined in Par 94 [Spd Reg Ki Base].

Default:

Min/Max:
Units:

Read Only

0.00 / 100.00
%

Real

88,
94

101

[Speed Thresh Pos]

Threshold speed for the drive above or below which the value of Par 393
[Speed Threshold] changes. When the speed of the drive exceeds the value of
this parameter, Par 393 [Speed Threshold] displays “Above Thresh” (0). When
the speed of the drive is below the value of this parameter, Par 393 [Speed
Threshold] displays “Below Thresh” (1).
Note: See Speed Threshold Indicators on page

291

for more information.

Default:

Min/Max:
Units:

1000

1 / 6000
rpm

16-bit
Int

393

102

[Speed Thresh Neg]

Threshold speed for the drive above or below which the value of Par 393
[Speed Threshold] changes. When the speed of the drive exceeds the value
specified in this parameter, Par 393 [Speed Threshold] displays “Above
Thresh” (0). When the speed of the drive is below this threshold, Par 393
[Speed Threshold] displays “Below Thresh” (1).
Note: See Speed Threshold Indicators on page

291

for more information.

Default:

Min/Max:
Units:

1000

1 / 6000
rpm

16-bit
Int

393

103

[Threshold Delay]

Amount of time that must elapse before indication that the drive speed is
above the value set in Par 101 [Speed Thresh Pos] or below the value set in
Par 102 [Speed Thresh Neg].
Note: See Speed Threshold Indicators on page

291

for more information.

Default:

Min/Max:
Units:

100

0 / 65535
ms

16-bit
Int

393

104

[At Speed Error]

Defines the speed above and below the speed reference (in Par 118 [Speed
Reg In]) at which the value of Par 394 [At Speed] changes. When the
difference between the speed reference and the actual speed is greater than
the value of this parameter, Par 394 [At Speed] displays “Not Equal” (0).
When the difference between the speed reference and the actual speed is
less than the value of this parameter, Par 394 [At Speed] displays “Equal” (1).
Note: See Speed Threshold Indicators on page

291

for more information.

Default:

Min/Max:
Units:

100

1 / 6000
rpm

16-bit
Int

394

105

[At Speed Delay]

Amount of time that must elapse before indication that the drive speed
reference is within the range specified in Par 104 [At Speed Error] occurs.
Note: See Speed Threshold Indicators on page

291

for more information.

Default:

Min/Max:
Units:

100

0 / 65535
ms

16-bit
Int

394

106

[Ref Zero Level]

Speed below which speed references are equal to zero speed. Switch used in
the Speed Zero function.
Note: See Speed Threshold Indicators on page

291

for more information.

Default:

Min/Max:
Units:

20

1 / 6000
rpm

16-bit
Int

123,
124,
125,
126

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

A

A

A

A

A

A

A

A