Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 182

Advertising
background image

182

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 3

Programming and Parameters

INPUT / OUT

P

UT

Anal

og O

u

tp

ut

s

66
67
68
69

[Anlg Out1 Sel]
[Anlg Out2 Sel]
[Anlg Out3 Sel]*
[Anlg Out4 Sel]*

Selects the source of the value that drives the analog output.
*This parameter is used to configure an analog output on the
I/O Expansion circuit board. See

Appendix F

- Optional Analog and Digital I/O

Expansion Circuit Board.
Options:

Default:
Default:
Default:
Default:

12 =
13 =
18 =
14 =

“Motor Speed”
“Motor Curr”
“Fld Current”
“Motor Volts”

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

No.

Option (Par)

Scaling of Analog Output Value

No.

Option (Par)

Scaling of Analog Output Value

0 = “Off” (Not used)

n/a

18 = “Fld Current” (Par 234)

0-10V = 0-100% of Par 280 [Nom Mtr Fld
Amps]

1 =

“Spd Ref Out” (Par 385)

±10V = ±100% of Par 45 [Max Ref Speed] 19 = “UserDefined0” (Par 503)

±10V = ±2047 in Par 503 [UserDefined0]

2 =

“Trim Ramp” (Par 42)

±10V = ±100% of Par 45 [Max Ref Speed] 20 = “UserDefined1” (Par 504)

±10V = ±2047 in Par 504 [UserDefined1]

3 =

“Ramp In” (Par 110)

±10V = ±100% of Par 45 [Max Ref Speed] 21 = “UserDefined4” (Par 507)

±10V = ±2047 in Par 507 [UserDefined4]

4 =

“Ramp Out” (Par 113)

±10V = ±100% of Par 45 [Max Ref Speed] 22 = “UserDefined5” (Par 508)

±10V = ±2047 in Par 508 [UserDefined5]

5 =

“Spd Draw Out” (Par 1018)

±10V = ±100% of Par 45 [Max Ref Speed] 23 = “UserDefined6” (Par 509)

±10V = ±2047 in Par 509 [UserDefined6]

6 =

“Trim Speed” (Par 43)

±10V = ±100% of Par 45 [Max Ref Speed] 24 = “Field Ref” (Par 500)

(1)

(1)

Not used for permanent magnet motor applications.

0-10V = 0-100% of Par 280 [Nom Mtr Fld
Amps]

7 =

“Spd Reg In” (Par 118)

±10V = ±100% of Par 45 [Max Ref Speed] 25 = “PID Output” (Par 774)

±10V = ±10000 in Par 774 [PID Output]

8 =

“Spd Reg Out” (Par 236)

±10V = ± 100% of Par 179 [Nom Mtr Arm
Amps]

26 = “Out Volt Lvl” (Par 921)

±10V = ±100% Par 175 [Rated Motor Volt]

9 =

“Torque Ref” (Par 14)

±10V = ± 100% of Par 179 [Nom Mtr Arm
Amps]

27 = “Fld Cur Max” (Par 467)

0-10V = 0-100% of Par 280 [Nom Mtr Fld
Amps]

10 = “Trim Torque” (Par 40)

±10V = ± 100% of Par 179 [Nom Mtr Arm
Amps]

28 = “Filtered Spd” (Par 924)

±10V = ±100% of Par 45 [Max Ref Speed]

11 = “Torq Reg In” (Par 41)

±10V = ± 100% of Par 179 [Nom Mtr Arm
Amps]

29 = “Filtered Cur” (Par 928)

±10V = ± 200% of Par 179 [Nom Mtr Arm
Amps]

12 = “Motor Speed” (Par 121)

±10V = ±100% of Par 45 [Max Ref Speed] 30 = “Output Power” (Par 1052)

±10V = ± 200% of Par 179 [Nom Mtr Arm
Amps] x Par 175 [Rated Motor Volt]

13 = “Motor Curr” (Par 199)

±10V = ± 200% of Par 179 [Nom Mtr Arm
Amps]

31 = “Roll Diam” (Par 1154)

0-10V = 0-100% of Par 1153 [Max
Diameter]

14 = “Motor Volts” (Par 233)

±10V = ±100% of Par 175 [Rated Motor
Volt]

32 = “Tension Ref” (Par 1180)

0-10V = 0-100% of Par 1153 [Max
Diameter]

15 = “Analog In 1” (Par 70)

±10V = ±10V on Analog Input 1

33 = “Torque Curr” (Par 1193)

±10V = ± 200% of Par 179 [Nom Mtr Arm
Amps]

16 = “Analog In 2” (Par 75)

±10V = ±10V on Analog Input 2

34 = “Winder Ref” (Par 1217)

±10V = ±100% of Par 45 [Max Ref Speed]

17 = “Analog In 3” (Par 80)

±10V = ±10V on Analog Input 3

35 = “Active Comp” (Par 1213)

±10V = ± 200% of Par 179 [Nom Mtr Arm
Amps]

Advertising