Chapter 1

Installation and Wiring

Figure 12 - High Resistance Ground

Grounding the wye secondary neutral through a resistor is an acceptable method
of grounding. Under a short circuit secondary condition, any of the output
phases to ground will not exceed the normal line to line voltage. The resistor is
often used to detect ground current by monitoring the associated voltage drop.

Table 8 - Drive Modifications to Support Ungrounded Wye Neutral or Impedance Grounded
Connections

Frame

Circuit Board

Jumper/Connection

Figure to see for Details

A

Pulse Transformer (FIR1-xx-xx)

Remove jumper S9

Figure 13

on page

37

B

Pulse Transformer (FIR2-xx-xx)

Remove jumper S9

Figure 14

on page

37

C

Pulse Transformer (FIR3-xx-xx)

Remove jumper S9

Figure 15

on page

38

Transient Noise Filter (FIL-31)

Disconnect the filter board yellow/
green (ground) wire from the PE
connection on the drive chassis

Figure 16

on page

38

D

Pulse Transformer (FIR-D-xx-xx)

Remove capacitors C121 and C122

Figure 17

on page

39

Overvoltage Clipping (CFSF-xxx)

Remove jumper S1

Figure 18

on page

39