Figure 57 - Drive Status Indicators

#

Name

Color

State

Description

1 STS

(Status)

Green

Flashing

Drive ready, but not running and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing, Drive
Stopped

A condition exists that is preventing the drive from starting. Check
parameters 1403 [Start Inhibits] and/or 1380 [Drive Alarm 1].

Flashing, Drive
Running

An intermittent type 1 alarm condition is occurring. Check parameter
1380 [Drive Alarm 1]. See Fault Descriptions on page

202

and/or Alarm

Descriptions on page

206

.

Steady,
Drive Running

A continuous type 1 alarm condition exists. Check parameter 1380 [Drive
Alarm 1]. See Fault Descriptions on page

202

and/or Alarm Descriptions

on page

206

.

Red

Flashing

A fault has occurred. Check [Fault x Code] or view the Fault Queue on the
HIM. See Fault Descriptions on page

202

.

Steady

A non-resettable, non-configurable fault has occurred. Check [Fault x
Code] or view the Fault Queue on the HIM. See Fault Descriptions on page

202

.

2 PORT

Refer to the Communication
Adapter User Manual.

Status of DPI port internal communications (if present).

MOD

Status of communications module (when installed).

NET A

Status of network (if connected).

NET B

Status of secondary network (if connected).

STS

PORT

MOD

NET A

NET B