Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

145

Programming and Parameters

Chapter 3

DYNAMIC C

O

N

TROL

Ramp Ra

tes

20

[Ramp Delay]

Defines a ramp delay time when the ramp is active. Works with par [Digital Outx
Sel] set to 6 “Ramp Pos” or 7 “Ramp Neg”.

Default:

Min/Max:
Units:

100

0 / 65535
ms

16-bit
Int

113,
346,
347

22

[MOP Accel Time]

The acceleration rate for the MOP reference in response to a digital input. The MOP
acceleration rate = Par 2 [Maximum Speed] / Par 22 [MOP Accel Time].
If “0” is entered in this parameter, the ramp output directly follows the reference
value.

Default:

Min/Max:
Units:

10

0 / 65535
s

16-bit
Int

2

24

[Accel Time 2]

Sets the rate of acceleration for linear ramp 2.
Acceleration rate for ramp 2 = Par 2 [Maximum Speed] / Par 24 [Accel Time 2].

Default:

Min/Max:
Units:

10

0 / 65535
s

16-bit
Int

2

30

[MOP Decel Time]

The deceleration rate for the MOP reference in response to a digital input. The MOP
deceleration rate = Par 2 [Maximum Speed] / Par 30 [MOP Decel Time].

Default:

Min/Max:
Units:

10

0 / 65535
s

16-bit
Int

2

32

[Decel Time 2]

Sets the rate of deceleration for linear ramp 2.
Deceleration rate for ramp 2 = Par 2 [Maximum Speed] / Par 32 [Decel Time 2].

Default:

Min/Max:
Units:

10

0 / 65535
s

16-bit
Int

2

245

[Speed Ramp En]

Enables or disables the ramp function. The Ramp Reference block is bypassed
when this parameter is set to 0 “Disabled”.

Default:

Options:

1 =

0 =
1 =

“Enabled”

“Disabled”
“Enabled”

16-bit
Int

344

[Zero Ramp Output]

Activates either the ramp output (1) or the brake function (0). When this
parameter is set to 0 “Active”, the drive brakes through the maximum available
torque and the motor will perform a Current Limit Stop. Two quadrant drives do
not support a brake option.
“Active” = The ramp output is disabled and Pars 113 [Ramp Out] and 114

[Ramp Out Pct] are immediately set to zero.

“Not Active” = The ramp output is enabled. and Pars 113 [Ramp Out] and 114

[Ramp Out Pct] follow the Ramp Reference block commands.

Default:

Options:

1 =

0 =
1 =

“Not Active”

“Active”
“Not Active”

16-bit
Int

345

[Zero Ramp Input]

Activates or deactivates the ramp input.
“Active” = The ramp input is not active and Pars 110 [Ramp In] and 111 [Ramp

In Pct] = 0.

“Not Active” = The ramp input is activated and Pars 110 [Ramp In] and 111

[Ramp In Pct] correspond to the set reference.

Default:

Options:

1 =

0 =
1 =

“Not Active”

“Active”
“Not Active”

16-bit
Int

110,
111

373

[Freeze Ramp]

Determines whether the last ramp output reference value is retained or whether
the ramp output reference value is active.
“Active” = The value of the ramp output at the time of activation is retained

irrespective of any possible reference value changes at the ramp input.

“Not Active” = The ramp output value follows the ramp input value according

to the Ramp Reference Block commands.

Default:

Options:

1 =

0 =
1 =

“Not Active”

“Active”
“Not Active”

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

Par 113 [Ramp Out]

Par 346 [Torque Positive]

Par 347 [Torque Negative]

Par 20

[Ramp Delay]

A

A

A