Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 149

Advertising
background image

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

149

Programming and Parameters

Chapter 3

DYNAMIC

C

O

NTROL

Adapt

v Re

gul

at

or

189

[Adaptive I Gain1]

Integral gain for the range from zero to Par 184 [Adaptive Spd 1]. The value in this
parameter is defined as percentage of the value defined Par 94 [Spd Reg Ki Base].
Note: See Adaptive Speed Regulator on page

287

for more information.

Default:

Min/Max:
Units:

1.00

0.00 / 100.00
%

Real

94,
184

190

[Adaptive P Gain2]

Proportional gain for the range of values defined beginning with the value of Par
184 [Adaptive Spd 1] to the value defined in Par 185 [Adaptive Spd 2]. The value in
this parameter is defined as percentage of the value defined Par 93 [Spd Reg Kp
Base].
Note: See Adaptive Speed Regulator on page

287

for more information.

Default:

Min/Max:
Units:

10.00

0.00 / 100.00
%

Real

93,
184,
185

191

[Adaptive I Gain2]

Integral gain for the range of values defined beginning with the value of Par 184
[Adaptive Spd 1] to the value defined in Par 185 [Adaptive Spd 2]. The value in this
parameter is defined as percentage of the value defined Par 94 [Spd Reg Ki Base].
Note: See Adaptive Speed Regulator on page

287

for more information.

Default:

Min/Max:
Units:

1.00

0.00 / 100.00
%

Real

94,
184,
185

192

[Adaptive P Gain3]

Proportional gain for the range of values beginning above the value defined in Par
185 [Adaptive Spd 2]. The value in this parameter is defined as percentage of the
value defined Par 93 [Spd Reg Kp Base].
Note: See Adaptive Speed Regulator on page

287

for more information.

Default:

Min/Max:
Units:

10.00

0.00 / 100.00
%

Real

93,
185

193

[Adaptive I Gain3]

Integral gain for the range of values beginning above the value defined in Par 185
[Adaptive Spd 2]. The value in this parameter is defined as percentage of the value
defined Par 94 [Spd Reg Ki Base].
Note: See Adaptive Speed Regulator on page

287

for more information.

Default:

Min/Max:
Units:

1.00

0.00 / 100.00
%

Real

94,
185

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

A

A

A

A