Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

83

Installation and Wiring

Chapter 1

Digital Encoder Terminal Block

The encoder connection cables should always be connected directly to the
terminals on the encoder terminal block. The encoder cable must be made up of
twisted pairs with the shield connected to the shield ground on the drive side. Do
not connect the shield to ground on the motor side. In some cases (for example,
cable lengths that exceed 100 meters), it may be necessary to ground the shield of
each twisted pair on the power supply. See page

214

for Digital Encoder

specifications.

Figure 53 - Digital Encoder Terminal Block Location

Table 37 - Digital Encoder Terminal Designations

Terminal Block

Label

Signal

Description

A+

Encoder A

Single channel A or dual channel
quadrature A input

A-

Encoder A (NOT)

B+

Encoder B

Single channel B or dual channel
quadrature B input

B-

Encoder B (NOT)

Z+

Encoder Z

Pulse, marker or registration input

(2)

(2) Selectable via switch S20 on the control board. See

Table 26

on page

54

.

Z-

Encoder Z (NOT)

COM

+5/12…15V

(1)

DC Return

Internal power common

+V

+5/12…15V

(1)

DC Power

(1) Selectable via switch S21 on the control board. See

Table 26

on page

54

.

Internal power source
200 mA

Digital Encoder

terminal block

Control board

EMI shield

Wire shield ground

Wire shield ground

A-

B+

B-

Z+

A+

COM

+V

Z-