Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 146

Advertising
background image

146

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 3

Programming and Parameters

DYN

A

MIC C

O

NTROL

Ramp

Ra

tes

660

[Accel Time 1]

Sets the rate of acceleration for linear ramp 1.
Acceleration rate for ramp 1 = Par 2 [Maximum Speed] / Par 660 [Accel Time 1].

Default:

Min/Max:
Units:

10

0 / 65535
s

16-bit
Int

2

662

[Decel Time 1]

Sets the rate of deceleration for linear ramp 1.
Deceleration rate for ramp 1 = Par 2 [Maximum Speed] / Par 662 [Decel Time 1].

Default:

Min/Max:
Units:

10

0 / 65535
s

16-bit
Int

2

665

[S Curve Accel 1]

Amount of time (approximately half at the start and half at the end) applied to the
S-curve during Accel 1 changes. When Par 19 [S Curve Time] is changed this
parameter is automatically set to the same value. For asymmetrical S-curve ramps,
set this parameter after [S Curve Time] is changed.
Note: See S-curve Configuration on page

284

for more information.

Default:

Min/Max:
Units:

1.00

0.10 / 15.00
s

Real

19

666

[S Curve Decel 1]

Amount of time (approximately half at the start and half at the end) applied to the
S-curve during Decel 1 changes. When Par 19 [S Curve Time] is changed this
parameter is automatically set to the same value. For asymmetrical S-curve ramps,
set this parameter after [S Curve Time] is changed.
Note: See S-curve Configuration on page

284

for more information.

Default:

Min/Max:
Units:

1.00

0.10 / 15.00
s

Real

19

667

[S Curve Accel 2]

Amount of time (approximately half at the start and half at the end) applied to the
S-curve during Accel 2 changes. When Par 19 [S Curve Time] is changed this
parameter is automatically set to the same value. For asymmetrical S-curve ramps,
set this parameter after [S Curve Time] is changed.
Note: See S-curve Configuration on page

284

for more information.

Default:

Min/Max:
Units:

1.00

0.10 / 15.00
s

Real

19

668

[S Curve Decel 2]

Amount of time (approximately half at the start and half at the end) applied to the
S-curve during Decel 2 changes. When Par 19 [S Curve Time] is changed this
parameter is automatically set to the same value. For asymmetrical S-curve ramps,
set this parameter after [S Curve Time] is changed.
Note: See S-curve Configuration on page

284

for more information.

Default:

Min/Max:
Units:

1.00

0.10 / 15.00
s

Real

19

1410 [Jog Ramp Time]

Sets the rate of acceleration and deceleration while the Jog function is active. The
Jog rate = Par 2 [Maximum Speed] / Par 1410 [Jog Ramp Time].
Note: This parameter was added for firmware version 2.001.

Default:

Min/Max:
Units:

10

0 / 65535
s

16-bit
Int

2

Lo

ad

Li

m

it

s

13

[Torq Red CurLim]

The armature current limit, defined as a percentage of the value defined in Par 179
[Nom Mtr Arm Amps] when Par 342 [Torque Reduction] is set to 1 “Active”.

Default:

Min/Max:
Units:

100

0 / 200
%

16-bit
Int

342

696

[Droop Percent]

Droop function gain is a percentage of the ratio between Par 45 [Max Ref Speed]
and the difference of Par 698 [Load Comp] – Par 41 [Current Reg In]. Therefore,
when the difference between Par 698 [Load Comp] and Par 41 [Current Reg In] =
100% and Par 696 [Droop Percent] = 100%, the speed reference correction signal
is equal to Par 45 [Max Ref Speed].
Note: See Droop Compensation on page

271

for more information.

Default:

Min/Max:
Units:

0.00

0.00 / 100.00
%

Real

41,
45,
698

697

[Droop Filter]

Droop filter time constant for the Droop function.
Note: See Droop Compensation on page

271

for more information.

Default:

Min/Max:
Units:

0

0 / 1000
ms

16-bit
Int

698

[Load Comp]

The load compensation signal. This value is typically equal to the “master” drive’s
current. The load compensation signal is a percentage of I

dn

.

Default:

Min/Max:
Units:

0

+ / –200
%

16-bit
Int

699

[Enable Droop]

Enables/Disables the Droop function.
“Enabled” = The Droop function is enabled.
“Disabled” = The Droop function is disabled.
Notes: This parameter can be assigned to a digital input. See Droop Compensation
on page

271

for more information.

Default:

Options:

0 =

0 =
1 =

“Disabled”

“Disabled”
“Enabled”

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

A

A

A

A

A

A

A

A