I/o converter board wiring – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 346

Advertising
background image

346

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Appendix G

Optional 115V AC to 24V DC I/O Converter Circuit Board

I/O Converter Board Wiring

Table 93 - Recommended Signal Wire Size

A 75 x 2.5 x 0.4 mm (3.0 x 0.1 x 0.02 in.) flathead screwdriver is recommended
for connecting wire to the terminal block inputs. Strip the ends of the cables to a
length of 6.5 mm (0.26 in.).

Table 94 - I/O Converter Board M_IN Terminal Block Designations

Table 95 - I/O Converter Board M_OUT Terminal Block Designations

Wire Type and Size

Tightening Torque
N

m (lb

in)

Flexible (mm

2

)

multi-core (mm

2

)

AWG

0.14…1.5

0.14…1.5

28…16

0.4 (3.5)

No.

Signal

Description

1

Digital Input 1

Rated input voltage:115V AC ±10%
50…60Hz.
ON input voltage: 115V AC ±10%
OFF input voltage: 0 - 70V AC
ON input current: 4…5.5 mA

2

Digital Input 2

3

Digital Input 3

4

Digital Input 4

5

Digital Input 5

6

Digital Input 6

7

Digital Input 7

8

Digital Input 8

Com Digital Input Common

No.

Signal

Description

24V

+24VDC Supply

24V DC ±10%, 40 mA power supply. Max. load
120 mA.
Supply power can be provided by the +24V DC
supply on the control board I/O (terminal 19 -
see

Figure 98

on page

347

) or an external

source (see

Figure 99

on page

347

).

1

Digital Output 1

Output type: Open collector, PNP type with 15
k

Ω

pull-down

Output current: 10 mA max.
Delay time hw OFF to ON: 5 ms (typ.)
Delay time hw ON to OFF: 50 ms (typ.)

2

Digital Output 2

3

Digital Output 3

4

Digital Output 4

5

Digital Output 5

6

Digital Output 6

7

Digital Output 7

8

Digital Output 8

0V

24V Common

Common for the power supply.
· If an internal supply is used, this terminal

must be wired to the digital input
common (terminal 16 or 35) on the
control board I/O. See

Figure 98

on page

347

.

· If an external supply is used, this terminal

must be wired to the external 24V DC
supply common and the digital input
common (terminal 16 or 35) on the
control board I/O. See

Figure 99

on page

347

.

2

3

4

5

1

7

8

6

CO

M

1

2

3

4

24V

6

7

8

0V

5