Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 105

Advertising
background image

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

105

Drive Start Up

Chapter 2

5.

Press the Start button on the HIM. This will start the speed regulator
auto tuning test, which could take several minutes. When the test has
been completed, the drive will automatically stop.

During the test the following are completed:

An acceleration test, with the torque limit value set in the Par 1048
[Autotune Cur Lim].

A deceleration test, with a lower torque limit value applied, until
zero speed has been reached.

Par 1013 [Torque Const] is calculated and updated based on the
entered motor data.

The test threshold speed is 33% of the lowest value set in the following
parameters:

45 [Max Ref Speed]

3 [Max Speed Fwd] or 4 [Max Speed Rev] based on the rotation
direction chosen in Par 1029 [Speed Tune Dir]

The drive will determine the speed loop gains (Pars 87 [Spd Reg Kp] and
88 [Spd Reg Ki]) based on the motor and load inertia and friction
characteristics.

If any fault occur during the test, see Auto Tuning Faults on page

107

for a

description and more information.

Note:

If any manual adjustments are required (due to vibrations, etc.),
these should be carried out according to the value of the
integral gain Par 88 [Spd Reg Ki]. If the speed regulator auto
tuning test does not provide satisfactory results, see Fine
Tuning the Regulators
on page

301

.

The values determined by the Speed Regulator tuning tests are updated in
Pars 87 [Spd Reg Kp], 88 [Spd Reg Ki], 1014 [Inertia] and 1015 [Friction]
and displayed in the corresponding Pars 1032 [Speed Tune Kp], 1033
[Speed Tune Ki], 1030 [Spd Tune Inertia] and 1031 [SpdTune Friction],
respectively. The values of Pars 1030 - 1033 can be used as a record of the
Speed Regulator auto tuning results if the values of Pars 87, 88, 1014 and
1015 are subsequently changed.