Par 1045 [Anlg In1 Cmp Eq] = “1” (high) when the signal on Analog
Input 1 is within the range specified in Par 1043 [Anlg In1 Cmp Err]. Par
1045 [Anlg In1 Cmp Eq] = “0” (low) when the signal on Analog Input 1 is
outside the range specified in Par 1043 [Anlg In1 Cmp Err].

Example 2:

An application requires an indication via a digital output that the output current
is within ±2% of 50% of the maximum current limit.

Par 7 [Current Limit] = 100% (maximum reference value)

For Analog Input 1, 10V or 20mA sets the maximum value = Par 7
[Current Limit]

Configure the following:

Set Par 70 [Anlg In1 Sel] = “Pos Cur Lim”

Set [Digital Outx Sel] = “Input1 Cmp” (Par 1045 [Anlg In1 Cmp Eq])

Set Par 1042 [Anlg In1 Cmp] = 5000 (50 x 10000 / 100)

Set Par 1043 [Anlg In1 Cmp Err] = 200 (2 x 10000 / 100 )

Current / Speed Curve

The current/speed curve function allows you to establish a current limit lower
than the standard current limits of the drive (specified in parameters 8 [Current
Lim Pos] and 9 [Current Lim Neg]) and reduce the output current (torque) of
the drive through a defined curve of five equally divided set points as the speed
increases based on a threshold speed, effectively reducing torque.

Par 10 [Cur Lim Pos Out]

or

Par 11 [Cur Lim Neg Out]

Par 751 [TrqTpr Lim0]

Current/Speed

Par 162 [Max Feedback Spd]

Par 752 [TrqTpr Lim1]

Par 753 [TrqTpr Lim2]

Par 754 [TrqTpr Lim3]
Par 755 [TrqTpr Lim4]

Par 756 [TrqTpr Spd]

Curr

en

t

Speed