Control circuit input power, Ontro, L ci – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual
Page 65: T in, T po, Rcui, T input po, Ntro

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013
65
Installation and Wiring
Chapter 1
Control Circuit Input Power
The control circuit must be powered by an external 230V AC or 115V AC single
phase power supply. For frame B and C drives only, a jumper is required between
terminals SA and SB for 115V AC control input power. For frame B drive SA-SB
terminal block location, see
Figure 43
on page
67
. For frame C drive SA-SB
terminal block location, see
Figure 43
on page
67
.
Note:
If the SA-SB terminal block is not configured for the correct input voltage,
“No Fault” (F0) will display on the HIM, if installed.
Table 19 - Control Circuit Wire Sizes and Terminal Specifications
Figure 39 - Frame A Control Circuit Terminal Block Location
Figure 40 - Frame B Control Circuit Terminal Block Location
Terminals
Description
U2, V2
Single phase AC power for the control circuits
PE
Safety ground (on frame C drive terminal blocks only)
Terminals
Wire Size and Type
(1)
(1) See Cable and Wiring Recommendations on page
for more information.
Tightening Torque
N
•m (lb•in)
Flexible
(mm
2
)
Multi-core
(mm
2
)
AWG
U2, V2
0.14…1.5
0.14…2.5
26…14
0.5 (4.4)
PE
2.5…10
2.5…10
12…8
2.0 (18.0)
U2
V2
U2
V2