Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

65

Installation and Wiring

Chapter 1

Control Circuit Input Power

The control circuit must be powered by an external 230V AC or 115V AC single
phase power supply. For frame B and C drives only, a jumper is required between
terminals SA and SB for 115V AC control input power. For frame B drive SA-SB
terminal block location, see

Figure 43

on page

67

. For frame C drive SA-SB

terminal block location, see

Figure 43

on page

67

.

Note:

If the SA-SB terminal block is not configured for the correct input voltage,

“No Fault” (F0) will display on the HIM, if installed.

Table 19 - Control Circuit Wire Sizes and Terminal Specifications

Figure 39 - Frame A Control Circuit Terminal Block Location

Figure 40 - Frame B Control Circuit Terminal Block Location

Terminals

Description

U2, V2

Single phase AC power for the control circuits

PE

Safety ground (on frame C drive terminal blocks only)

Terminals

Wire Size and Type

(1)

(1) See Cable and Wiring Recommendations on page

44

for more information.

Tightening Torque
N

m (lbin)

Flexible
(mm

2

)

Multi-core
(mm

2

)

AWG

U2, V2

0.14…1.5

0.14…2.5

26…14

0.5 (4.4)

PE

2.5…10

2.5…10

12…8

2.0 (18.0)

U2

V2

U2

V2