201

Troubleshooting

Chapter 4

HIM Indicators

The LCD HIM also provides visual notification of a fault or alarm condition.

Manually Clearing Faults

Condition

Display

The drive is indicating a fault.
The LCD HIM immediately reports the fault condition by displaying the
following:

• “Faulted” appears in the status line
• Fault number
• Fault name
• Time that has passed since the fault occurred

Press “Esc” to regain HIM control.
The drive is indicating an alarm.
The LCD HIM immediately reports the alarm condition by displaying the
following:

• Alarm name
• Alarm bell graphic

F-> Faulted

Auto

0.0

Hz

Main Menu:

Diagnostics

Parameter

— Fault — F 5
Arm OverVoltage
Time Since Fault

0000:23:52

F-> DigInCflctA

Auto

0.0

rpm

Main Menu:

Diagnostics

Parameter

Device Select

Step

Key(s)

1. Press “Esc” to acknowledge the fault. The fault information will be removed so that you can

use the HIM.

2. Address the condition that caused the fault.

The cause must be corrected before the fault can be cleared.

3. After corrective action has been taken, clear the fault by one of these methods.

• Press “Stop”
• Cycle drive power
• Set parameter

1347

[Fault Clear] to 1 “Clear Faults”

• “Clear Faults” on the HIM Diagnostic menu

Esc