Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 312

Advertising
background image

312

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Appendix C

Application Notes

Curve B - If the field current curve fine tuning procedure is completed, the
flux current to flux reference curve will follow a curve determined by the
real flux percentage of Par 500 [Flux Ref Pct] necessary to determine the
circulation of the field current for the connected system. See the Current
Regulator block diagram on

page 326

.

Field Current Curve Tuning Procedure:

1.

Reset the field current curve by setting Par 920 [Reset Fld Curve] to “1”.

2.

Configure the following parameters:

❏ Enter the percentage (100%) of the maximum motor nameplate rated

armature voltage in Par 921 [Out Volt Level]

❏ Set Par 469 [Field Mode Sel] = 0 “Base Speed”

❏ Set Par 467 [Max Fld Curr Pct] = 100%

3.

Start the drive.

4.

Increase the motor speed until the value (electromotive force) displayed in
Par 233 [Output Voltage] corresponds to the value previously set in Par 175
[Rated Motor Volt].

5.

Decrease the value of Par 467 [Max Fld Curr Pct] until the value displayed in
Par 233 [Output Voltage] is equal to 90% of Par 175 [Rated Motor Volt].
When you have reached this value, read the value displayed in Par 234 [Fld
Current Pct] and enter the value into Par 918 [Fld Const 90 Pct].

6.

Decrease the value of Par 467 [Max Fld Curr Pct] until the value displayed in
Par 233 [Output Voltage] is equal to 70% of Par 175 [Rated Motor Volt].
When you have reached this value, read the value displayed in Par 234 [Fld
Current Pct] and enter the value into Par 917 [Fld Const 70 Pct].

7.

Decrease the value of Par 467 [Max Fld Curr Pct] until the value displayed in
Par 233 [Output Voltage] is equal to 40% of Par 175 [Rated Motor Volt].
When you have reached this value, read the value displayed in Par 234 [Fld
Current Pct] and enter the value into Par 916 [Fld Const 40 Pct].

8.

Stop the drive.

9.

Set the desired method of field control in Par 469 [Field Mode Sel] (0 “Base
Speed” or 1 “Field Weaken”)

10.

Reset the value of 467 [Max Fld Curr Pct] to 100%.

If you change the value of Par 175 [Rated Motor Volt] or par 280 [Nom Mtr Fld
Amps], the field current curve will need to be re-tuned.

Advertising