Dc output voltages, Typical power wiring diagrams, E typical power wiring diagrams and – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 46: Dc output voltages typical power wiring diagrams

Advertising
background image

46

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 1

Installation and Wiring

Control Circuit (Terminals U2, V2)

115V ±15% or 230V ±15%, 1Ph

Note: For frame B and C drives only, a jumper must be placed between terminals
SA-SB on the Switching Power Supply circuit board for the control circuits to
work with 115V AC input. See

Figure 43

on page

67

for terminal block location

on frame B drives and

Figure 44

on page

67

for terminal block location on frame

C drives.

DC Output Voltages

The output voltages below take into account an AC input undervoltage within
the stated tolerance limits and a voltage drop of 4% due to an AC input line
reactor. It is the same as the rated armature voltage suggested for the connected
motor.

Armature Circuit

Field Circuit

Typical Power Wiring Diagrams

Figure 19

on page

47

Figure 21

on page

49

represent recommended power

wiring configurations for standard PowerFlex DC drive installations. For SAR
installations, see

Appendix H

.

AC Input Voltage

DC Output Armature Voltage (Terminals C & D)

(Terminals U, V, W)

Two Quadrant Drive

Four Quadrant Drive

230V ±10 %, 3Ph

260V

240V

400V ±10 %, 3Ph

470V

420V

440V ±10 %, 3Ph

530V

460V

460V ±10 %, 3Ph

560V

480V

480V ±10 %, 3Ph

580V

500V

575V ±10 %, 3Ph

680V

600V

690V ±10 %, 3Ph

810V

720V

AC Input Voltage

DC Output Field Voltage

(1)

(Terminals C1 & D1)

(1) The max field voltage is equal to 0.85 x AC input line voltage

(Terminals U1 & V1)

Fixed Field

Adjustable Field

230V ±10 %, 1Ph

200V

200V

400V ±10 %, 1Ph

310V

310V

460V ±10%, 1Ph

360V

360V