Frame d overvoltage clipping circuit board fuses – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 237

Advertising
background image

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

237

Supplemental Drive Information

Appendix A

Frame D Overvoltage Clipping Circuit Board Fuses

The following fuses are used to protect the resistors and capacitors on the
Overvoltage Clipping circuit board for frame D drives only.

The Overvoltage

Clipping circuit board is located on the left side wall inside the drive
enclosure, behind the control panel.

Figure 77 - Frame D Overvoltage Clipping Circuit Board Fuse Locations

Circuit Board ID / Revision

Designation

Fuse (14 x 51 mm)

CFSFxxx / All

F11/F21/F31

10 A, 690V fast

Overvoltage Clipping board fuse locations (shown with control panel open).