Frame c and d fuse information – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 225

Advertising
background image

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

225

Supplemental Drive Information

Appendix A

Frame C and D Fuse Information

All fuses for armature and field circuit protection are internally mounted and
provided with frame C and D drives.

Figure 65 - Frame C and D Fuse Table Designations

Frame C and D Recommended Field Circuit Fuses

Field circuit fuses for frames C and D drives are internally mounted (labeled FU1
and FV1) and provided with the drive. See Fuse Code FS3 in

Figure 65

above.

Also, see

Figure 66

on page

226

and

Figure 67

on page

227

for locations.

Table 55 - 230V AC Input Drives

Table 56 - 460V AC Input Drives

Fr

am

e

Drive
Current
Rating
Code

Field
Amps

Type

Qty Bussmann

Ferraz Shawmut (Gould
Shawmut)

SIBA

C

521

20

10 x 38 mm

2

FWC-25A10F

A60Q25-2

6003305.25

D

875

40

22 x 58 mm

FWP-50A22F

A70QS50-22F

5014006.50

1K0

Fram

e

Drive
Current
Rating
Code

Field
Amps

Type

Qty

Bussmann

Ferraz Shawmut
(Gould Shawmut)

SIBA

C

495

20

10 x 38 mm

2

FWC-25A10F

A60Q25-2

6003305.25

667

A60Q25-8

D

830

40

22 x 58 mm

FWP-50A22F

A70QS50-22F

5014006.50

996
1K1

70

FWP-100A22F

A70QS100-22F

5014006.100

1K3
1K4

U V W

C D

FS3

FS4

C1 D1

U1 V1

M

FS3 = Internally
mounted fuses for
the field circuit on
the AC input side.

FS4 = Internally
mounted fuses for
the armature
converter on the AC
input side.

Advertising