Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 128

Advertising
background image

128

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 3

Programming and Parameters

MO

TO

R C

O

NTROL

To

rq A

ttri

but

es

12

[Current Rate Lim]

Specifies the largest change in armature current reference that will be
allowed per current loop scan (2.7 ms @ 60Hz, 3.3 ms @ 50Hz AC line
frequency). A value of 100% indicates that the armature current reference
will not be permitted to change by more than rated motor current in a given
speed loop scan period.
Note: This parameter was added for firmware version 5.002.

Default:

Min/Max:
Units:

25

0.1 / 250
%

Real

39

[Torque Ref]

First current reference value, before any trim signals are incorporated, as a
percentage of the value set in Par 179 [Nom Mtr Arm Amps]. For firmware
version 2.005 or lower, this parameter is only used when Par 242 [Speed Reg
En] = 0 "Disabled".
Note: The current reference value is proportional to the armature current of
the motor and determines the torque. The polarity determines the torque
direction.

Default:

Min/Max:
Units:

0

– / +200
%

Real

40

[Trim Torque]

Second current reference value as a percentage of the value set in Par 179
[Nom Mtr Arm Amps]. [Trim Torque] is added to Torque Reference and can be
used as a correction value for the torque reference (regardless of the value of
Par 242 [Speed Reg En]).

Default:

Min/Max:
Units:

0

– / +200
%

Real

342

[Torque Reduction]

Selection for torque reduction. When the torque reduction function is active
(1 “Active”), the current limit changes accordingly by the percentage defined
in Par 13 [Torq Red CurLim]. When this parameter is set to 0 “Not Active”,
torque reduction is not active.
For example:

Par 7 [Current Limit] (or Pars 8 [Current Lim Pos] and 9 [Current Lim Neg])
= 80 %
Par 13 [Torq Red CurLim] = 70%
If Par 342 [Torque Reduction] = 0 “Not Active”, the current limit = 80 %
If Par 342 [Torque Reduction] = 1 “Active”, the current limit = 70 %

Note: This parameter can be assigned to a digital input.

Default:

Options:

0 =

0 =
1 =

“Not Active”

“Not Active”
“Active”

16-bit
Int

13

353

[Zero Torque]

Sets the reference value for the armature current (Par 41 [Current Reg In]) to
zero so that the drive has no torque.
“Not Active” = Par 41 [Current Reg In] is not set to zero.
“Active” = Par 41 [Current Reg In] is set zero. The drive has no torque.

Default:

Options:

1 =

0 =
1 =

“Not Active”

“Active”
“Not Active”

16-bit
Int

41

750

[TrqTpr Enable]

Enables/Disables the current/speed curve function.
“Disabled” = The limits current /speed curve is disabled
“Enabled” = The limits current /speed curve is enabled
Note: See Current / Speed Curve on page

264

for more information.

Default:

Options:

0 =

0 =
1 =

“Disabled”

“Disabled”
“Enabled”

16-bit
Int

751,
752,
753,
754,
755,
756

751

[TrqTpr Lim0]

The current limit of the current/speed curve that operates constantly up to
the speed set in Par 756 [TrqTpr Spd]. When the current/speed curve function
is enabled (set in Par 750 [TrqTpr Enable]), this parameter will override the
current limits set in Pars 10 [Cur Lim Pos Out] and 11 [Cur Lim Neg Out].

Default:

Min/Max:
Units:

0

0 / 200
%

16-bit
Int

750,
756

752

[TrqTpr Lim1]

First reduced current limit of the current/speed curve. The value defined in
this parameter must be less than the value in Par 751 [TrqTpr Lim0] and
greater than the values in Pars 753 [TrqTpr Lim2], 754 [TrqTpr Lim3] and 755
[TrqTpr Lim4].

Default:

Min/Max:
Units:

0

0 / 200
%

16-bit
Int

750,
756

753

[TrqTpr Lim2]

Second reduced current limit of the current/speed curve. The value defined in
this parameter must be less than the value in Par 752 [TrqTpr Lim1] and
greater than the values in Pars 754 [TrqTpr Lim3] and 755 [TrqTpr Lim4].

Default:

Min/Max:
Units:

0

0 / 200
%

16-bit
Int

750,
756

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

A

A

A

Advertising