Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 162

Advertising
background image

162

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 3

Programming and Parameters

APPL

IC

AT

IONS

Sc

al

e B

lo

ck

s

486
555
1220
1229
1238
1247

[Scale1 Mul]
[Scale2 Mul]
[Scale3 Mul]
[Scale4 Mul]
[Scale5 Mul]
[Scale6 Mul]

Multiplier of the input quantity (after a possible limitation). Resolution:
5 digits. See the Scale Blocks block diagram on page

331

for more information.

Default:

Min/Max:

1.00

–/+10000.00

Real

487
556
1221
1230
1239
1248

[Scale1 Div]
[Scale2 Div]
[Scale3 Div]
[Scale4 Div]
[Scale5 Div]
[Scale6 Div]

Divisor, through which it is possible to divide the input quantity already multiplied
and limited. Resolution: 5 digits. See the Scale Blocks block diagram on page

331

for more information.

Default:

Min/Max:

1.00

–/+10000.00

Real

488
557
1222
1231
1240
1249

[Scale1 In Max]
[Scale2 In Max]
[Scale3 In Max]
[Scale4 In Max]
[Scale5 In Max]
[Scale6 In Max]

Maximum limit of the input quantity. Resolution: 5 digits. See the Scale Blocks
block diagram on page

331

for more information.

Default:

Min/Max:

0.00

– 2

31

/ +2

31

– 1

Real

489
558
1223
1232
1241
1250

[Scale1 In Min]
[Scale2 In Min]
[Scale3 In Min]
[Scale4 In Min]
[Scale5 In Min]
[Scale6 In Min]

Minimum limit of the input quantity. Resolution: 5 digits. See the Scale Blocks
block diagram on page

331

for more information.

Default:

Min/Max:

0.00

– 2

31

/ +2

31

– 1

Real

490
559
1224
1233
1242
1251

[Scale1 In Off]
[Scale2 In Off]
[Scale3 In Off]
[Scale4 In Off]
[Scale5 In Off]
[Scale6 In Off]

Offset to be added to the input quantity. Resolution: 5 digits. See the Scale Blocks
block diagram on page

331

for more information.

Default:

Min/Max:

0.00

– 2

31

/ +2

31

– 1

Real

491
560
1225
1234
1243
1252

[Scale1 Out Off]
[Scale2 Out Off]
[Scale3 Out Off]
[Scale4 Out Off]
[Scale5 Out Off]
[Scale6 Out Off]

Offset to be added to the output quantity. Resolution: 5 digits. See the Scale Blocks
block diagram on page

331

for more information.

Default:

Min/Max:

0.00

– 2

31

/ +2

31

– 1

Real

492
561
1226
1235
1244
1253

[Scale1 In Abs]
[Scale2 In Abs]
[Scale3 In Abs]
[Scale4 In Abs]
[Scale5 In Abs]
[Scale6 In Abs]

Controls how the input value is processed.
“Off” = The input quantity is processed with its sign.
“On” = The input quantity is processed with a positive sign (absolute value).
It is possible to have the polarity change with the signs of the [ScalexMul] or
[ScalexDiv] parameters. See the Scale Blocks block diagram on page

331

for more

information.

Default:

Options:

0 =

0 =
1 =

“Off”

“Off”
“On”

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

A

A

A

A

A

A

Advertising