Frame C and D Armature Fuse Signal Terminals

Terminals 81 and 82 on frame C and D drives are connected to the internal
armature circuit protection fuses and can be connected to an external device to
provide indication that the fuses have opened. Alternatively, terminals 81 and 82
can be wired to drive digital input terminals configured for 64 “Invert Flt” (via
Pars 133…144).

Table 24 - Armature Fuse Signal Terminal Designations

Table 25 - Armature Fuse Signal Wire Size and Terminal Specifications

Figure 47 - Frame C Internal Armature Fuse Signal Terminal Block Location

Terminal

Description

Maximum Voltage

Maximum Current

81

Internal armature fuse intervention signal.

250V AC

1 A

82

Terminals

Wire Size and Type

(1)

(1) See Cable and Wiring Recommendations on page

44

for more information.

Tightening Torque
N

m (lbin)

Flexible
(mm

2

)

Multi-core
(mm

2

)

AWG

81,

82

0.14…1.5 0.14…2.5 26…16

0.4

(3.5)

81

82