Table 18 - Relay Outputs and Thermistor/Thermal Switch Wire Sizes and Specifications

Figure 35 - Frame A Relay and Thermistor/Thermal Switch Terminal Block Locations

Figure 36 - Frame B Relay and Thermistor/Thermal Switch Terminal Block Locations

Signal Type

Terminals

Wire Size and Type

(1)

(1) See Cable and Wiring Recommendations on page

44

for more information.

Tightening
Torque
N

m (lbin)

Flexible
(mm

2

)

Multi-core
(mm

2

)

AWG

Relay Outputs

35 & 36, 75 & 76

0.140…1.500

0.140…1.500

26…14

0.5 (4.4)

Thermistor and
Thermal Switches

78 & 79

78

79

35

36

75

76

Note: Terminals 78 and 79 shown with 1
k

Ω

resistor in place of temperature sensor.

78 79 35 36 75 76