Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 310

Advertising
background image

310

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Appendix C

Application Notes

Field Voltage Regulator Tuning Examples

Figure 91 - Field voltage oscillation

Oscillation after a speed change where [Arm Volt Kp] = 10% and [Arm Volt Ki]
= 80%.
Top: Par 234 [Fld Current Pct]
Bottom: Par 233 [Output Voltage]

Figure 92 - Too small of a gain

The armature voltage increases where [Arm Volt Kp] = 3% and [Arm Volt Ki] =
5%.
Top: Par 234 [Fld Current Pct]
Bottom: Par 233 [Output Voltage]

Figure 93 - Optimal field regulation

After a short transient, the field current and armature voltage are constant.
[Arm Volt Kp] = 40%, [Arm Volt Ki] = 5%.
Top: Par 234 [Fld Current Pct]
Bottom: Par 233 [Output Voltage]

Advertising