Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

269

Application Notes

Appendix C

Example 5: Encoder with Field Weakening

This example is similar to example 4 except that an encoder is configured so there
is no feedback scaling required.

Par 175 [Rated Motor Volt] = 500V (default)

Set Par 45 [Max Ref Speed] = 2500 rpm

Set Par 162 [Max Feedback Spd] = 2500 rpm

Set Par 169 [Encoder PPR] = 240 ppr

Set Par 585 [Overspeed Val] = 2750 rpm

The reference and feedback resolution = (7500 fpm/25000 counts) = 0.3
fpm/count

Speed Feedback

Regardless of the type of speed feedback device used, (selected in Par 414 [Fdbk
Device Type]), the value of parameters 162 [Max Feedback Spd] and 169
[Encoder PPR] must be in the allowed area shown in

Figure 79

on page

270

based on the value of Par 175 [Rated Motor Volt].