The motor reaches maximum speed immediately, Testpoint codes and functions – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual
Page 210

210
Rockwell Automation Publication 20P-UM001I-EN-P - February 2013
Chapter 4
Troubleshooting
The motor reaches maximum speed immediately
Testpoint Codes and
Functions
Select a testpoint with Par
[TestPoint Sel]. Values can be viewed with Par
[TestPoint Data].
Drive Symptom
Action
The motor accelerates to maximum speed and cannot be
controlled.
Check the analog input voltage and speed reference values:
• Parameters 1404 [Analog In1 Value], 1405 [Analog In2 Value], 44 [Speed Ref A] and 48 [Speed Ref B]
• Check the setting of switch S9 and parameter 71 [Anlg In1 Config], S10 and 76 [Anlg In2 Config] or S11 and 81
[Anlg In3 Config].
The feedback device, encoder, resolver, or DC analog tachometer is not connected/configured, incorrectly connected
or has failed.
• Change parameter 414 [Fdbk Device Type] to 3 “Armature” to test the encoder or DC analog tachometer feedback.