Chapter 3

Programming and Parameters

MOT

O

R C

O

NTROL

Fie

ld Con

fig

469

[Field Mode Sel]

Operating mode of the field controller.
“Base Speed” = The motor field is regulated with constant current and

controls the motor from zero to base speed. If a curve is defined through
Pars 916, 917 and 918 [Fld Const xx Pct], this value will change linearly
through Par 467 [Max Fld Curr Pct] (which is a percentage of the nominal
flux value set in Par 280 [Nom Mtr Fld Amps]).

“Field Weaken” = The motor field is regulated with a combination of

torque and constant power (armature and field regulation -- field
weakening). The maximum armature voltage is configured in Par 175
[Rated Motor Volt]. When using a DC contactor, this parameter is set to
this option, and Par 458 [SpdReg FB Bypass] is set to 1 “Enabled,” the
armature voltage feedback terminals A1 and A2 must be connected to the
motor terminals A1 and A2, respectively.

“External” = The motor field power is supplied by an external rectifier/

converter (the drive’s field output is disabled).

“PM External” = External field created by a permanent magnet (PM)

motor.

Note: Option 3 “PM External” was added for firmware version 5.002.

Default:

Options:

0 =

0 =
1 =
2 =
3 =

“Base Speed”

“Base Speed”
“Field Weaken”
“External”
“PM External”

16-bit
Int

456,
916,
917,
918,
921

497

[Field Reg Enable]

Enables/Disables the field regulator. Leave set to the default value for
permanent magnet motor applications.
“Enabled” = The field regulator is enabled and controlling the field

output.

“Disabled” = The field regulator is disabled (the field current is zero).

Default:

Options:

1 =

0 =
1 =

“Enabled”

“Disabled”
“Enabled”

16-bit
Int

498

[Force Min Field]

Enables/Disables the minimum field current value. Leave set to the default
value for permanent magnet motor applications.
“Enabled” = The field current corresponds to the value set via Par 468

[Min Fld Curr Pct].

“Disabled” = The field current is regulated based on the quadrant mode

and situation in which the drive is operating.

Note: This parameter can be assigned to a digital input (35 “Force MinFld”).

Default:

Options:

0 =

0 =
1 =

“Disabled”

“Disabled”
“Enabled”

16-bit
Int

499

[Field Economy En]

When this parameter is set to 1 = “Enabled” and the value in Par 107 [Speed
Zero Level] is reached (after the amount of time specified in Par 1407 [Field
Econ Delay] has elapsed), the minimum field current (set via Par 468 [Min Fld
Curr Pct]) is produced. Leave set to the default value for permanent magnet
motor applications.
“Disabled” = Disables field economy
“Enabled” = Enables field economy

Default:

Options:

1 =

0 =
1 =

“Enabled”

“Disabled”
“Enabled”

16-bit
Int

395,
468,
1407

916

[Fld Const 40 Pct]

Current value at 40% of the rated field flux. Leave set to the default value for
permanent magnet motor applications.

Default:

Min/Max:
Units:

40.00

0.00 / 100.00
%

Real

469

917

[Fld Const 70 Pct]

Current value at 70% of the rated field flux. Leave set to the default value for
permanent magnet motor applications.

Default:

Min/Max:
Units:

70.00

0.00 / 100.00
%

Real

469

918

[Fld Const 90 Pct]

Current value at 90% of the rated field flux. Leave set to the default value for
permanent magnet motor applications.

Default:

Min/Max:
Units:

90.00

0.00 / 100.00
%

Real

469

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

ATTENTION: Enabling (forcing) the minimum field current while the drive is running could result in excessive motor
speed, equipment damage, and/or bodily injury.