Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 204

Advertising
background image

204

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 4

Troubleshooting

Port 1-5 Adapter

71…75

2

The communications card has a fault.

Check the DPI device event queue and corresponding fault
information for the device.

Port 1-5 DPI Loss

81…85

2

The DPI port stopped communicating.

1. Check the HIM connection.
2. If adapter was not intentionally disconnected, check the wiring

to the port. Replace the wiring, port expander, adapters, control
board or complete drive as required.

3. If an adapter was intentionally disconnected and the bit for that

adapter in Par

591

[Logic Mask] is set to “1”, this fault will occur.

To disable this fault, set the appropriate bit in [Logic Mask] for
the adapter to “0.”

Power Failure

3

2

Possible causes include:

There is a fault in the 24V control board supply - the voltage is
below the permitted value. In most cases the cause is in the
external I/O wiring.

Pull the plug-in I/O terminal blocks out of the control circuit

board and reset the drive via

1347

[Fault Clear]. If there are no

other faults, check the I/O wiring for a short-circuit including the
cable shielding.

Check fuses F1 and F2 located on the Switching Power Supply

circuit board (frame A size drives only have one fuse - F1).
Replace as necessary.*

Check varistor fuses F1, F2, and F3 on the Pulse Transformer or

Transient Noise Filter circuit boards for Frame C size drives.
Replace as necessary.*

If this fault occurs again, an internal fault may be present.

Contact your Rockwell Automation sales office.

*Note: See Control Power Circuit Protection Fuses on page

233

for

fuse sizing information.

The incoming voltage to the control power terminals (U2, V2)
is too low due to:
The AC input voltage is too low
There are poor cable connections.
The fuse(s) on the switching power supply circuit board

have blown.

Verify AC input power level.
Check all connections.
Check and replace the fuse(s) if necessary.

Resolver Error

93

2

An error was detected with the resolver signal while it was
configured for use by the drive.

1. Verify the resolver wiring.
2. Verify the resolver configuration in Pars

423

[Reslvr Type Sel],

424

[Reslvr Spd Ratio], and

425

[Resolver Config].

3. Verify the resolver power supply.

Spd Fdbk Loss

91

1

The speed feedback device selected by Par

414

[Fdbk Device

Type] is indicating less than 5% of Par

162

[Max Feedback

Spd] while the measured armature voltage is greater than the
value of Par

455

[Spd FB Loss Lvl].

Possible causes include:
The conductors of the feedback signal have been

interrupted.

Current from one or more of the feedback device wires is not
reaching the drive. Check the feedback device wiring.

One or several encoder/resolver channels are missing

(conductor interruption, no power supply).

Check the encoder/resolver connections and power supply.

The motor voltage is incorrect.

1. Verify that Par

175

[Rated Motor Volt] is set correctly

2. Tune the motor.

The ramp rate is too fast for the connected load.

1. Reduce the load.
2. Reduce the ramp rate.

Field Weakening is set incorrectly.

Verify the that the value of Par

456

[Fld Weaken Ratio] is set

properly.

The encoder or resolver configuration is incorrect.

1. For encoder feedback, verify the setting of DIP switch S20 (see

page

73

) and Par

652

[Encoder Err Chk].

2. Verify that the connected encoder is capable of the input and

output voltage as determined by DIP switch S21 (see page

73

).

3. For resolver feedback, verify that Par

426

[Resolver Status] is not

indicating any errors.

Note: This fault condition can be configured to produce an alarm with Par

478

[Spd Loss Flt Cfg].

STune Aborted

62

2

The speed regulator auto tuning procedure has been stopped
by the user.

Informational only.

Fault Name

Number Type

(1)

Description/Possible Cause(s)

Action(s)

IMPORTANT

Remove power from the drive before removing the I/O terminal blocks and/or
fuses.