Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 122

Advertising
background image

122

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 3

Programming and Parameters

MO

NIT

OR

Cu

rrent Met

ers

232

[Inertia Comp Out]

Displays the output of the Inertia Compensation function. The [Inertia Comp
Out] signal (if selected by Par 1016 [SpdFuncSelect]) is summed with Pars 14
[Selected TorqRef] and 40 [Trim Torque]. Inertia compensation provides a
torque feed forward signal during changes in motor speed reference.
Note: This parameter was added for firmware version 4.001.

Default:

Min/Max:
Units:

Read Only

–/+200
%

Real

234

[Fld Current Pct]

Field current (present value) as a percentage of Par 280 [Nom Mtr Fld Amps].
When running a permanent magnet motor, this parameter will display zero.
Note: This parameter can be assigned to an analog output and is the default
value for Par 68 [Anlg Out3 Sel].

Default:

Min/Max:
Units:

Read Only

0.00 / 100.00
%

Real

280

236

[Spd Reg Out Pct]

Output value of the speed regulator, as a percentage of Par 179 [Nom Mtr
Arm Amps], used as the reference for the current regulator.

Default:

Min/Max:
Units:

Read Only

–/+250
%

Real

179

351

[Field Current]

Present value of the field current. When running a permanent magnet motor,
this parameter will display zero.
Note: This parameter can be assigned to an analog output.

Default:

Min/Max:
Units:

Read Only

0.00 / 99.90
A

Real

476

[Field Curve Out]

Displays the output value of the field current used as a reference to the field
current regulator.
Note: This parameter was added for firmware version 4.001.

Default:

Min/Max:
Units:

Read Only

0.00 / 100.00
%

Real

500

[Flux Ref Pct]

Field flux (reference) as a percentage of Par 280 [Nom Mtr Fld Amps]. When
running a permanent magnet motor, this parameter will display zero.
Notes: This parameter can be assigned to an analog output. This name of this
parameter was changed from [Field Ref Pct] for firmware version 3.001.

Default:

Min/Max:
Units:

Read Only

0.00 / 100.00
%

Real

280

928

[Filt TorqCur Pct]

Filtered value of Par 1193 [Torq Current Pct]. The amount of filtering is set by
Par 926 [Torq Cur Filter].

Default:

Min/Max:
Units:

Read Only

–/+250
%

16-bit
Int

926,
1193

Dr

iv

e Da

ta

57

[FaultCode]

A code that represents the fault that tripped the drive. See Fault Descriptions
on page

202

for a list of fault codes and descriptions.

Default:

Min/Max:

Read Only

0 / 65535

16-bit
Int

233

[Output Voltage]

Measured output armature voltage.
Note: This parameter can be assigned to an analog output and is the default
selection for Par 69 [Anlg Out4 Sel].

Default:

Min/Max:
Units:

Read Only

-/+999.00
Vdc

Real

235

[Elapsed Lifetime]

Shows the operating time of the drive. This parameter counts the time for
which the drive is energized (even if the drive is disabled).

Default:

Min/Max:
Units:

Read Only

0.00 / 65535.0
H.m

Real

300

[Drive Type]

Displays of the drive type.
“10” = Non-Regenerative
“11” = Regenerative

Default:

Min/Max:

Read Only

10 / 11

16-bit
Int

331

[Software Version]

Displays the Major and Minor (Major.Minor) firmware version numbers active
in the drive.

Default:

Min/Max:

Read Only

1.00 / 999.00

Real

465

[Drive Size]

Armature current rating (as indicated by the configuration of DIP switch S15
on the control board). This value is used to determine the Drive Overload fault
(F64).
Note: S15 is set to the appropriate value at the factory. However, if the control
board was supplied separate from the drive and installed as a replacement
part, S15 must be manually set to the appropriate drive size. See DIP Switch
and Jumper Settings on page

72

.

Default:

Min/Max:
Units:

Read Only

0 / Based on drive current rating
A

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted