Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 3

Programming and Parameters

INPUT

/ OU

TPU

T

D

igi

ta

l O

u

tpu

ts

581

[Dig Out Status]

Status of the standard digital outputs and relay outputs on the drive and on the optional I/O
Expansion circuit board (if present).

Read Only

629

[Relay Out 2 Sel]

Selects the source of the value that drives the N.O. relay between the
terminals 75 and 76.
See “Option Definitions” on page

187

.

Note: Option 16 “Encoder Err” was changed for firmware version
v5.002.Options:

Default:

5 =

“Ready”

16-bit
Int

1267
1268
1269
1270
1271
1272
1273
1274

[Inversion Out 1]
[Inversion Out 2]
[Inversion Out 3]
[Inversion Out 4]
[Inversion Out 5]
[Inversion Out 6]
[Inversion Out 7]
[Inversion Out 8]

Reverses the digital output signal.

Default:

Options:

0 =

0 =
1 =

“Disabled”

“Disabled”
“Enabled”

16-bit
Int

1275

[Inversion Relay2]

Inverts the signal for Relay Output 2.

Default:

Options:

0 =

0 =
1 =

“Disabled”

“Disabled”
“Enabled”

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

Options

Re

la

y O

ut2

Re

la

y O

ut1

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Di

gi

ta

l Ou

t8

Di

gi

ta

l Ou

t7

Di

gi

ta

l Ou

t6

Di

gi

ta

l Ou

t5

Di

gi

ta

l Ou

t4

Di

gi

ta

l Ou

t3

Di

gi

ta

l Ou

t2

Di

gi

ta

l Ou

t1

Default

0

0

x

x

x

x

x

x

0

0

0

0

0

0

0

0

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0 =

“Not Used” (Off)

8 =

“Spd Limited”

16 = “Spd Fdbk Err”

24 = “ContactDB”

1 =

“Spd Zero Thr”

9 =

“Fault”

17 = “Diam Calc”

25 = “Contactor”

2 =

“Spd Thresh”

10 = “Power Loss”

18 = “Input1 Cmp”

26 = “Alarm”

3 =

“At Speed”

11 =

“UserDefinedA”

19 = “Diam Reached”

27 = “Running”

4 =

“CurrentLimit”

12 =

“UserDefinedB”

20 = “Speed Match”

28 = “Jogging”

5 =

“Ready”

13 = “Stop Control”

21 = “Accelerating”

29 = “Active”

6 =

“Ramp Pos”

14 =

“Field Loss”

22 = “Decelerating”

7 =

“Ramp Neg”

15 =

“Spd Fbk Loss”

23 = “Brake Cmd”

A

A