Fine Tuning the Speed Regulator

Follow the procedure below to fine tune and optimize the speed regulator:

1.

Configure the following Test Generator parameters:

❏ Set Par 58 [TstGen Output] = 4 “Ramp Ref ”

❏ Set Par 59 [TstGen Frequency] = 0.2 Hz

❏ Set Par 60 [TstGen Amplitude] = 10 %

❏ Set Par 61 [TstGen Offset] = 20 %

2.

Measure the results on analog outputs 1 and 2 by setting:

❏ Par 66 [Anlg Out1 Sel] = 8 “Spd Reg Out”

❏ Par 67 [Anlg Out2 Sel] = 13 “Motor Curr”.

3.

Set Par 660 [Accel Time 1] = 0 sec.

4.

Set Par 662 [Decel Time 1] = 0 sec.

5.

Set Par 87 [Spd Reg Kp] = 0.00

6.

88 [Spd Reg Ki] = 0.00

7.

Start the drive.

8.

Increase the value of Par 87 [Spd Reg Kp] until the overshoot is lower than
4% with the shortest possible acceleration or deceleration time.

9.

Increase the value of Par 88 [Spd Reg Ki] until the overshoot is higher than
4%. Then, decrease the value of this parameter until its value becomes
slightly lower than 4%.

10.

Stop the drive.

11.

Set Par 58 [TstGen Output] = 0 “NotConnected”.

When it is necessary to have different gains for the speed regulator above the
speed range, you can utilize the adaptive speed regulator. For further information
about this function see the Adaptive Speed Regulator block diagram page

287

.

IMPORTANT

When the “Bypass” function is enabled (Par 458 [SpdReg FB Bypass] = 1
“Enabled”) the drive is automatically switched to armature feedback when a
“Speed fbk loss” fault occurs due to an encoder or tachometer feedback loss. In
this case, you must repeat steps 1 - 9 of the “Fine Tuning the Speed Regulator”
procedure when the fault has been cleared. After an automatic switch to
armature feedback, the speed regulator works with Pars 459 [SpdReg Kp
Bypass] and 460 [SpdReg Ki Bypass] and the D (derivative) part of the speed
regulator is automatically excluded.