Cable and wiring recommendations, Example – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 44

Advertising
background image

44

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 1

Installation and Wiring

Cable and Wiring
Recommendations

Use the following cable and spacing recommendations for all drives sizes:

Example:

Spacing relationship between 480V AC incoming power leads and 24V DC logic
leads:

480V AC leads are Class 2; 24V DC leads are Class 6

For separate steel conduits, the conduits must be 3 inches (76 mm) apart

In a cable tray, the two groups of leads are to be 6 inches (152 mm) apart

Minimum Spacing Between Classes - Steel Conduit/Tray

Category Wiring

Class

Signal Definition

Signal Example

Cable Type

1

2/3/4

5/6

7/8

9/10/11

See Cable

Spacing

Notes, on

page

45

Power

1

AC Power (600V Or
Greater)

2.3kV 3/ph AC Lines

Per NEC & Local
Codes

0

3/9 in.

(76/229 mm)

3/9 in.

(76/229 mm)

3/18 in.

(76/457 mm)

See Note 6

1/2/5

2

AC Power (Less Than
600V)

460V 3/ph AC Lines

3/9 in.

(76/229 mm)

0

3/6 in.

(76/152 mm)

3/12 in.

(76/305 mm)

See Note 6

1/2/5

3

DC Power

DC Motor Armature

4

DC Power

DC Motor Field

Control

5

115V AC/DC Logic

Relay Logic/PLC I/O
Motor Thermostat

3/9 in.

(76/229 mm)

3/6 in.

(76/152 mm)

0

3/9 in.

(76/229 mm)

See Note 6

1/2/5

115V AC Power

Power Supplies,
Instruments

6

24V AC/DC Logic

PLC I/O

Signal
(Process)

7

Analog Signals, DC
Supplies

Reference/Feedback
Signal, 5 To 24V DC

Shielded Cable –
Belden 8735,
8737, 8404

3/18 in.

(76/457 mm)

3/12 in.

(76/305 mm)

3/9 in.

(76/229 mm)

0

1/3 in.

(25/76 mm)

2/3/4/5

Digital (Low Speed)

TTL

8

Digital (High Speed)

I/O, Encoder, Resolver,
Count Pulse Tach

Shielded Cable –
Belden 9728, 9730

Signal
(Comm.)

9

Serial Communication

RS-232 (20-COMM-R),
422 To Terminals/printers

Shielded Cable –
Belden RS-232 –
8735, 8737 RS-
422 – 9729, 9730

See Note 6

1/3 in.

(25/76 mm)

0

11

Serial Communication
(Greater Than 20k Baud)

PLC Remote I/O, PLC Data
Highway

Twinaxial Cable –
Belden 9463, A-B
1770-CD

Minimum Spacing Between Classes Steel Conduit/Tray

Category

Wiring
Class

Signal Definition

Signal Example

1

2/3/4

5/6

Power

2

AC Power (less
than 600V)

460V 3/Ph AC Lines

3/6 in.

(76/152 mm)

Control

6

24V AC/DC Logic

PLC I/O

3/6 in.

(76/152 mm)