Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 239

Advertising
background image

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

239

Supplemental Drive Information

Appendix A

Table 77 - 575V AC Input Drives

B

129

129

105.4

75

1321-3R160-B

56…75 (75…100)

100-D110D11

167

167

136.4

100

1321-3R160-B

56…75 (75…100)

100-D140D11

207

207

169.1

125

1321-3RB250-B

93…112 (125…150)

100-D180D11

250

250

204.3

150

1321-3RB250-B

93…112 (125…150)

100-D210ED11

330

330

269.6

200

1321-3RB320-B

149 (200)

100-D300ED11

412

412

336.6

250

1321-3RB400-B

186.4 (250)

100-D420ED11

C

495

495

404.4

300

1321-3R500-B

223.7 (300)

100-D420ED11

667

667

544.9

400

1321-3R600-B

298.3 (400)

100-D630ED11

D

830

830

678.1

500

1321-3R750-B

372.8 (500)

100-D860ED11

996

996

813.7

600

1321-3R850-B

447,4 (600)

100-D860ED11

1K1

1162

949.4

700

1321-3R1000-B

552 (700)

100-G860KD22

1K3

1328

1085.0

800

2 x1321-3R600-B

596.6 (800)

100-G860KD22

1K4

1494

1220.6

900

2 x1321-3R600-B

671.1 (900)

100-G1200KD12

Frame

Drive Current
Rating Code

DC Amps

AC Line
Amps

Hp

IP00 (Open Style)
Line Reactor Cat No.

Line Reactor kW (HP)

AC Input Contactor Cat. No.

Frame

Drive Current
Rating Code

DC Amps

AC Line Amps

Hp

IP00 (Open Style)
Line Reactor Cat No.

Line Reactor kW (HP)

AC Input Contactor Cat. No.

B

067

67.5

55.1

50

1321-3R55-B

37 (50)

100-C60D10

101

101.25

82.7

75

1321-3R100-B

56 (75)

100-C85D10

135

135

110.3

100

1321-3R130-B

75 (100)

100-D110D11

270

270

220.6

200

1321-3RB250-B

149 (200)

100-D250ED11

405

405

330.9

300

1321-3RB320-B

224 (300)

100-D420ED11

C

540

540

441.2

400

1321-3RB500-B

298 (400)

100-D630ED11

675

675

551.5

500

1321-3R600-B

373 (500)

100-D630ED11

D

810

810

661.8

600

1321-3R750-B

447 (600)

100-D860ED11

1K0

1080

882.4

800

1321-3R1000-B

597 (800)

100-G700KD22

1K2

1215

992.7

900

1321-3R1000-B

671 (900)

100-G860KD22

1K3

1350

1103.0

1000

2 x 1321-3R600-B

746 (1000)

100-G1000KD12

1K6

1687.5

1378.7

1250

2 X 1321-3R750-B

(1)

(1) No AC Input Contactor available for this drive rating - must be sourced locally.

Advertising