Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 207

Advertising
background image

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

207

Troubleshooting

Chapter 4

DigInCflctC

2

More than one physical input has been configured to the same input function. Multiple
configurations are not allowed for the following input functions.

Forward/Reverse

Run Reverse

Run Forward

Jog Forward

Jog Reverse

Speed Select 1

Speed Select 2

Speed Select 3

Acc2 / Dec2

Accel 2

Decel 2

Run

FB Cfg Cflct

2

One of the following has occurred:
Par

414

[Fdbk Device Type] does not equal 3 “Armature” and Par

478

[Spd Loss Flt Cfg] is

set to “Alarm” while Par

458

[SpdReg FB Bypass] is set to “Disabled”.

Par 414 [Fdbk Device Type] is set to 4 “Resolver” and Pars

429

[Resolver Pos Sel],

430

[Resolver Spd Sel],

786

[PID Source],

1204

[Line Spd Source], or

1284

[Ref Spd Source] are

selecting a resolver signal.

Par 414 [Fdbk Device Type] is set to 1 “Encoder” and Pars 786, 1021, 1204, or 1284 are

selecting an encoder signal.

FldCfg Cflct

2

The selected operating mode of the field controller is in conflict with another setting in the
drive or a permanent magnet motor is incorrectly configured. This alarm displays under the
following conditions:
Par

469

[Field Mode Sel] = “Field Weaken” or “External” and Par

458

[SpdReg FB Bypass]

= “Enabled”

Par 469 [Field Mode Sel] = “Field Weaken” or “External” and Par

414

[Fdbk Device Type]

= “Armature”

Par 469 [Field Mode Sel] = “Field Weaken” or “External” and Par

478

[Spd Loss Flt Cfg] =

“Alarm”

Par 469 [Field Mode Sel] = “Field Weaken” or “Base Speed” and Par

497

[Field Reg En] =

“Disabled”

Par 469 [Field Mode Sel] = “Base Speed” and Par

498

[Force Min Field] = “Enabled”

Par 469 [Field Mode Sel] = “Base Speed” and Par

133

144

[Digital Inx Sel] = “Force

Min Fld”

Fld Current Loss

1

The field current is too low. See the “Fld Current Loss” fault description on

page 202

for more

information.

Motor Overload

1

The selected motor overload current level has been exceeded. See the “Motor Overload” fault
description on

page 203

for more information.

Motor Over Temp 1

The motor has exceeded its temperature rating (as signaled by the thermistor connected to
the drive terminals 78 and 79). See the “Motor Over Temp” fault description on

page 203

for

more information.

Ref Cflct

2

1. More than one of the drive's reference inputs (Pars

70

,

75

and

80

[Anlg Inx Sel], Pars

1323

1327

[DPI Px Select], Par

1021

[Encoder Out Sel], or Par

430

[Resolver Spd Sel])

are set to the same value. See

Figure 80

on page

280

or Speed Reference Selection on

page

317

for a graphical representation of the drive's reference selections.

2. Both Pars

429

[Resolver Pos Sel] and

430

[Resolver Spd Sel] are non-zero.

3. More than one of the following parameters contains the same value:

786

[PID Source],

1204

[Line Spd Source], and

1284

[Ref Spd Source].

Spd Fdbk Err

1

With Par

478

[Spd Loss Flt Cfg] set to 1 “Alarm” an error condition associated with the

selected speed feedback device (analog tachometer, encoder, or resolver) was detected.

Spd Fdbk Loss

1

With Par

478

[Spd Loss Flt Cfg] set to 1 “Alarm”, the speed feedback device selected in Par

414

[Fdbk Device Type] is indicating less than 5% of Par

162

[Max Feedback Spd] while the

measured armature voltage is greater than the value of Par

455

[Spd FB Loss Lvl]. See the

“Spd Fdbk Loss” fault description on page

204

for more information.

Start At PowerUp 1

Par

1344

[Start At Powerup] is enabled. The drive may start at any time after drive power up

and the time specified in Par

1345

[Powerup Delay] has elapsed.

Alarm

Type

Description