Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 93

Advertising
background image

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

93

Drive Start Up

Chapter 2

16.

With the “Motor Data” group selected, press Enter.

17.

Configure the following parameters:

Note: Parameters 45 [Max Ref Speed] and 162 [Max Feedback Spd] are
typically set to the motor nameplate base speed. However, if a speed
feedback device is used (encoder or tachometer), see Drive Reference
and Feedback Scaling
on page

265

for details on setting these

parameters.

❏ 45 [Max Ref Speed] - Enter the motor nameplate base speed.

❏ 162 [Max Feedback Spd] - Enter the motor nameplate base speed.

❏ 175 [Rated Motor Volt] - Enter the rated motor nameplate

armature voltage. This value should be the measured armature
voltage when the motor is running at base speed with rated field
current. This value should represent 100% of the rated armature
voltage when field weakening is not used. If field weakening is used,
this value should be set to 90% of the rated armature voltage to
prevent a possible overvoltage condition when the drive transitions
to the field weakening mode.

❏ 179 [Nom Mtr Arm Amps] - Enter the rated motor nameplate

armature current. Note: the drive size (as set by DIP switch S15 and
shown in Par 465 [Drive Size]) should not exceed the motor size (as
set by Par 179) by more than three times to prevent current scaling/
resolution issues.

❏ 374 [Drv Fld Brdg Cur] - Enter the rated current of the field bridge

regulator to match the value set using the DIP switch S14. See Field
Current Configuration
on page

60

.

❏ 280 [Nom Mtr Fld Amps] - Enter the rated motor nameplate field

current. If using a permanent magnet motor, leave this parameter set
to the default value.