Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 185

Advertising
background image

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

185

Programming and Parameters

Chapter 3

INP

U

T / OUT

P

UT

D

igital Inputs

564

[Dig In Status]

Status of the digital inputs.

Read Only

565
566
567
568
569
570
571
572
573
574
575
576

[Dig In Term 1]
[Dig In Term 2]
[Dig In Term 3]
[Dig In Term 4]
[Dig In Term 5]
[Dig In Term 6]
[Dig In Term 7]
[Dig In Term 8]
[Dig In Term 9]
[Dig In Term 10]
[Dig In Term 11]
[Dig In Term 12]
Status of the digital inputs.
0 = Low
1 = High

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

1276
1277
1278
1279
1280
1281
1282
1283
1387
1388
1389
1390

[Inversion In 1]
[Inversion In 2]
[Inversion In 3]
[Inversion In 4]
[Inversion In 5]
[Inversion In 6]
[Inversion In 7]
[Inversion In 8]
[Inversion In 9]
[Inversion In 10]
[Inversion In 11]
[Inversion In 12]

inverts the digital input signal.

Default:

Options:

0

0 =
1 =

“Disabled”

“Disabled”
“Enabled”

16-bit
Int

1391

[ContactorControl]
Selects the type of contactor to be controlled by the drive. Either style of
contactor (AC or DC) can be used, with or without dynamic braking (DB)
contactor.
“AC Cntctr” indicates an AC contactor is used. See note 1 below.
“AC Cntctr+DB” indicates that an AC contactor and dynamic brake

resistor is used. See note 1 below.

“DC Cntctr” indicates a DC contactor is used.
“DC Cntctr+DB” indicates that a DC contactor and dynamic brake resistor

is used.

The type of control selected determines how many I/O points will be
required for contactor control and status.
“AC Cntctr” or “DC Cntctr” = 1 (relay) digital output, 1 digital input is

used.

“AC Cntctr+DB” or “DC Cntctr+DB” = 2 (relay) digital outputs, 1 digital

input is used.

Notes:
1. When 1 “AC Cntctr” or 2 “AC Cntctr+DB” is selected, there is a 400 ms

delay to power up before SCR firing can begin. The delay is needed to
determine correct input voltage phasing.

2. Option 1 was changed from “Contactor”, option 2 was changed from

“Contactor+DB”, and options 3 and 4 were added for firmware version
2.001.

Default:

Options:

1 =

0 =
1 =
2 =
3 =
4 =

“AC Cntctr”

“None”
“AC Cntctr”
“AC Cntctr+DB”
“DC Cntctr”
“DC Cntctr+DB”

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

D

igital

In12

D

igital

In11

D

igital

In10

Di

gi

ta

l I

n9

Di

gi

ta

l I

n8

Di

gi

ta

l I

n7

Di

gi

ta

l I

n6

Di

gi

ta

l I

n5

Di

gi

ta

l I

n4

Di

gi

ta

l I

n3

Di

gi

ta

l I

n2

Di

gi

ta

l I

n1

Default

x

x

x

x

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0