Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

171

Programming and Parameters

Chapter 3

UTILIT

Y

Al

arms

365

[OverTemp Flt Cfg]

Determines the response of the drive to a motor over temperature condition (F16
“Motor Over Temp”).
Notes: See Chapter 4 for a list of alarm and fault descriptions. Option 3 was
changed from “Quick Stop” for firmware version 2.001.

Default:

Options:

2 =

0 =
1 =
2 =
3 =
4 =
5 =

“Fault”

“Ignore”
“Alarm”
“Fault”
“Fast Stop”
“Normal Stop”
“CurrLim Stop”

16-bit
Int

473

[FldLoss Flt Cfg]

Determines the response of the drive to a field loss condition (F6 “Fld Current
Loss”). If Par 497 [Field Reg Enable] is set to 0 “Disabled”, this parameter should be
set to 0 “Ignore”.
Note: See Chapter 4 for a list of alarm and fault descriptions.

Default:

Options:

2 =

0 =
1 =
2 =

“Fault”

“Ignore”
“Alarm”
“Fault”

16-bit
Int

497

478

[Spd Loss Flt Cfg]

Determines the response of the drive to a speed feedback loss condition.
Note: See Chapter 4 for a list of fault and alarm descriptions.

Default:

Options:

2 =

1 =
2 =

“Fault”

“Alarm”
“Fault”

16-bit
Int

458

479

[MtrOvrld Flt Cfg]

Determines the response of the drive to a motor overload condition (F7 “Motor
Overload”).
Notes: See Chapter 4 for a list of fault and alarm descriptions. This parameter was
added for firmware version 3.001.

Default:

Options:

2 =

0 =
1 =
2 =

“Fault”

“Ignore”
“Alarm”
“Fault”

16-bit
Int

376,
1290

481

[UnderVolt Thresh]

The AC input voltage level below which an undervoltage fault (F4 “AC
Undervoltage”) will be detected. A typical value is 85% of the nominal AC line
voltage (Par 466 [AC Line Voltage]). This fault can only occur while the drive is
running.
Note: See Chapter 4 for a list of fault descriptions.

Default:

Min/Max:
Units:

230

0 / 1000
Vac

16-bit
Int

584

[OverCurrent Thr]

Value at which an overcurrent condition (F13 “Overcurrent”) will be detected.
Note: See Chapter 4 for a list of fault descriptions.

Default:

Min/Max:
Units:

175

0 / 250
%

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 110

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

ATTENTION: Setting this parameter to 0 “Ignore” or 1 “Alarm”, could result in motor and/or equipment damage. If set to
“Ignore” or “Alarm”, it is strongly recommended that an external means of protecting against this condition be provided.

A

ATTENTION: Setting this parameter to 0 “Ignore” or 1 “Alarm”, could result in motor and/or equipment damage. If set to
“Ignore” or “Alarm”, it is strongly recommended that an external means of protecting against this condition be provided.

A

ATTENTION: Par 478 [Spd Loss Flt Cfg] must be set to 1 “Fault” if Par 458 [SpdReg FB Bypass] is set to 0 “Disabled”. Failure
to observe this precaution could result in high motor speeds, equipment damage, and/or bodily injury if a “Spd Fdbk Loss”
alarm condition were encountered.

A

ATTENTION: Setting Par 479 [MtrOvrld Flt Cfg] to 0 “Ignore” or 1 “Alarm”, could result in motor and/or equipment damage.
Ensure that the motor is properly sized for the application and that a separate device is installed that monitors for and
signals a motor overload condition.