Installation and Wiring

Chapter 1

Analog Output Bipolar Signal

±

10V Bipolar (based on the signal of

the assigned input source - for
example Analog Input 1)
or
0…10V Unipolar (shown)

Select Source Value:

66 [Anlg Out1 Sel]

Adjust Scaling:

62 [Anlg Out1 Scale]

Enable Input
24V DC internal supply

No Changes Required.

Note: If the digital input used for
“Enable” is changed from the
default setting of digital input 4,
the wiring must be changed
accordingly.

2-Wire Control Non-Reversing
24V DC internal supply

Important: Programming inputs
for 2-wire control deactivates the
HIM Start and Jog buttons.

Disable Digital Input 1:

133 [Digital In1 Sel]
= 0 “Not Used”

Set Digital Input 2:

134 [Digital In2 Sel]
= 5 “Run”

2-Wire Control
Reversing
24V DC external supply

Important: Programming inputs
for 2-wire control deactivates the
HIM Start and Jog buttons.

Set Digital Input 1:

133 [Digital In1 Sel]
= 6 “Run Forward”

Set Digital Input 2:

134 [Digital In2 Sel]
= 7 “Run Reverse”

3-Wire Control
24V DC internal supply

No Changes Required.

Input/Output

Connection Example

Required Parameter Changes

21

22

23

24

25

26

27

28

29

30

+

11

12

13

14

15

16

17

18

19

20

11

12

13

14

15

16

17

18

19

20

Stop-Run

Run Rev.

Run Fwd.

+24V

Neutral/

Common

11

12

13

14

15

16

17

18

19

20

11

12

13

14

15

16

17

18

19

20

Stop

Start

Advertising