Mounting considerations, Operating conditions and temperatures, Minimum mounting clearances – Rockwell Automation 20P PowerFlex Digital DC Drive User Manual

Page 18

Advertising
background image

18

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

Chapter 1

Installation and Wiring

Mounting Considerations

Operating Conditions and Temperatures

PowerFlex DC drives are designed to operate at 0…50 °C (32…122 °F)
surrounding air temperature without derating. The drive must be mounted in a
clean, dry location. Contaminants such as oils, corrosive vapors and abrasive
debris must be kept out of the enclosure. NEMA/UL Type Open, IP20
enclosures are intended for indoor use primarily to provide a degree of protection
against contact with enclosed equipment. These enclosures offer no protection
against airborne contaminants.

Minimum Mounting Clearances

Minimum clearance requirements (indicated in

Figure 1

) are intended to be from

drive to drive. Other objects can occupy this space; however, reduced airflow may
cause protection circuits to fault the drive. The drive must be mounted in a
vertical orientation as shown below and must not be mounted at an angle greater
than 30 degrees from vertical. In addition, inlet air temperature must not exceed
the product specification.

Figure 1 - Drive Enclosure Minimum Mounting Clearances

10 mm

10 mm

50 mm

(0.4 in.)

(0.4 in.)

(2.0 in.)

10 mm
(0.4 in.)

150 mm (6.0 in.)

150 mm (6.0 in.)

150 mm (6.0 in.)

STS

PORT

MOD

NET A

NET B

STS

PORT

MOD

NET A

NET B

Airflow through the

drive must not be

impeded.