DIP Switch S4 Settings

DIP switch S4 must be configured to be greater than or equal to the maximum
DC input voltage. Maximum DC Input Voltage = (Tach Volts/1000 rpm) x Par
45 [Max Ref Speed] x 1.1. See Drive Reference and Feedback Scaling on page

265

for details on programming speed feedback values.

Figure 50 - DC Analog Tachometer DIP Switch S4 Example

Table 27 - DC Analog Tachometer DIP Switch S4 Configuration

DIP Switch S15 Settings

DIP Switch S15 is configured for the appropriate drive size at the factory. Do not
change the settings unless you are installing a replacement control board.

Figure 51 - Drive Size DIP Switch S15 Example

ATTENTION: The drive can overspeed if DIP switch S4 is set incorrectly or the
tachometer is wired incorrectly. Failure to observe this precaution could result in
damage to, or destruction of, the equipment.

Maximum DC
Input Voltage

S4-1
S4-8

S4-2
S4-7

S4-3
S4-6

S4-4
S4-5

22V

ON

ON

ON

ON

45V

ON

ON

ON

OFF

90V

ON

ON

OFF

OFF

180V

ON

OFF

OFF

OFF

300V

OFF

OFF

OFF

OFF

1

ON

2

3

4

5

6

7

8

DIP

Note: The illustration depicts the DIP switch
settings for 90V (factory default).

1

ON

2

3

4

5

6

7

8

DIP

Note: Illustration for example only.