Rockwell Automation Publication 20P-UM001I-EN-P - February 2013

95

Drive Start Up

Chapter 2

20.

Access the “Utility” file.

21.

Press Enter.

22.

Access the “Alarms” group.

23.

Configure the following parameters:

❏ Par 481 [UnderVolt Thresh] - Enter the value at which an AC under

voltage condition will be detected by the drive (default = 200V on a
240V AC line and 400V on a 480V AC line). Typically, this value is
approximately 85% of the nominal AC line voltage.

❏ Par 584 [OverCurrent Thr] - Enter the value at which a drive over

current condition will be detected (default = 175%). The threshold
level should be at least 10% above the selected operating current
limit (Par 7 [Current Limit]).

❏ Par 585 [OverSpeed Val] - Enter a value that is 10% above the

maximum speed that the motor will achieve. Typically 10% above
Par 162 [Max Feedback Spd].

24.

Access the “Input & Output” file.

25.

Press Enter.

26.

Access the “Analog Inputs” group.

27.

Configure the following:

❏ If you have connected a potentiometer to analog input 1 for a speed

reference:

• Verify that Par 70 [Anlg In1 Sel] is set to 1 “Speed Ref A”

(default).

• Verify that switch S9 and Par 71 [Anlg In1 Config] are

configured to match (voltage versus a current signal). See DIP
Switch and Jumper Settings
on page

72

.

• Set Par 72 [Anlg In1 Scale] and Par 74 [Anlg In1 Offset]

appropriately.

❏ If you are using the HIM on the drive cover (Port 1) for the speed

reference, set Par 70 [Anlg In1 Sel] to 0 “Off ”.