Festo Контроллер позиционирования CPX-CMAX User Manual

Page 121

Advertising
background image

3. Drive functions

3−59

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

ć

Errors in the record parameters, e.g. an impermissible
switching condition (see section 3.3.3).

ć

Subsequent record with active record switching not initiaĆ
lised.

ć

If the next record is configured with an automatic profile,
only the condition MC (or none) are permissible. OtherĆ
wise, a warning (W37) is signaled and the free profile is
used.

ć

The CMAX does not react to the rising edge at
CPOS.START:
It must be checked whether SPOS.ACK was really reset.
After the PLC sets CPOS.START = 0 (Fig. 3/10

6 ), it must

wait for SPOS.ACK = 0 (Fig. 3/10

7 ). Otherwise, it may

be that the time for START = 0 is too short to be recogĆ
nised by the CMAX.

Notes regarding force control

If Force control" is set as the control mode with a rising edge
at CPOS.START in RCB1, the CMAX interprets the setpoint
specification as a force setpoint. It activates the force control
and adjusts the value with the parametrised ramp. The speed
is limited to the value in the Velocity" parameter.

When the setpoint value has been reached, taking into acĆ
count the tolerance, the MC" signal is set. The force is conĆ
trolled again until a new starting edge resets the controller
mode to positioning.
If the stroke or speed limits are exceeded, an error is sigĆ
naled. If there is a stop or error type F1 (controlled), there is a
switch to position control (set = actual, etc.).

Force tasks following positioning tasks with a relative setpoint
value refer to force 0.

Advertising