5. Parameter

5−43

Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH

5.4.5

Record list

Requested record number

PNU

PNU: 400

Index: 1

Max index: 3

Class: Struct

Data type: int32

Values

Without unit

Default: 0

Minimum: 0

Maximum: 64

The record number that was accepted with the last starting edge.
If no record was started yet, the value will be 0 (no permissible record number).

ý

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

o

After writing, controller recalculation is carried out.

Actual record number

PNU

PNU: 400

Index: 2

Max index: 3

Class: Struct

Data type: int32

Values

Without unit

Default: 0

Minimum: 0

Maximum: 64

The number of the record executed last.
If no record was executed yet, the value will be 0. This is no permissible record number.

ý

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

o

After writing, controller recalculation is carried out.

Record status byte

PNU

PNU: 400

Index: 3

Max index: 3

Class: Struct

Data type: bitarray

Values

Default:

0000 0000 0000 0000 0000 0000 0000 0000

Write:

Record status byte (RSB): contains a feedback code that is transferred to the input data.
In accordance with FHPP, only bits 0 ... 7 are defined. Bits 8 ... 31 are always 0. For a description of
the bits, see section 2.2.3.

ý

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

o

After writing, controller recalculation is carried out.