Festo Контроллер позиционирования CPX-CMAX User Manual

Page 271

Advertising
background image

5. Parameter

5−83

Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH

Position control filter factor

PNU

PNU: 1152

Index: 1

Max index: 1

Class: Var

Data type: int32

Values

Unit: Amplification (index = 10)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

Dimension Default

Minimum

Maximum

SI 0,01

100

10

1.000

0,01

100

10

1.000

Imperial 0,01

100

10

1.000

0,01

100

10

1.000

Position control filter factor, see section B.7

o

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

ý

This parameter can be written by FCT without higher−order controller.

ý

After writing, controller recalculation is carried out.

Position control timeout

PNU

PNU: 1153

Index: 1

Max index: 1

Class: Var

Data type: int32

Values

Unit: Time (index = 9)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

Dimension Default

Minimum

Maximum

SI 1 ms

2.000

0

100.000

1 ms

2.000

0

100.000

Imperial 1 ms

2.000

0

100.000

1 ms

2.000

0

100.000

Time within which the actual position must reach the tolerance window after the position setpoint
has reached the target value. This means the time starts when the setpoint value generation has
elapsed.
If the time is set to 0, no monitoring is carried out.
The time is additionally used for monitoring the start behaviour. If with a positioning task the drive
has not moved by at least 11 mm within the parametrised time after the start signal, a fault is generĆ
ated (setoff timeout")
Note:
Deactivation of the positioning timeout parameter may cause a record not to be concluded with MC
and to remain active permanently, e.g.:
Ĉ if the drive comes to a halt before its setpoint position (due to an obstacle),
Ĉ if the drive does not reach its setpoint position (depends on specified tolerance).

o

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

ý

After writing, controller recalculation is carried out.

Advertising