1 start of a positioning task, Start of a positioning task – Festo Контроллер позиционирования CPX-CMAX User Manual

Page 132

Advertising
background image

3. Drive functions

3−70

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

3.4.1

Start of a positioning task

t

min

t

min:

at least 1 bus cycle waiting time. Recommendation: 1 PLC cycle.

Not required if consistent data transmission is used.

Setpoint values
Output data

Start
CPOS.START (B1)

Acknowledge Start
SPOS.ACK (B1)

Motion Complete
SPOS.MC (B2)

N − 1

N

N + 1

1

0

1

0

1

0

1

0

N + 2

1

2

3

4

Fig. 3/11: Start the positioning task

The sequence of remaining control and status bits
behave according to record select operating mode.
See sections 3.3.1, Fig. 3/10.

1 The desired setpoint value (position, force) and the posiĆ

tioning condition (absolute/relative, speed or force ramp,
etc.) are set in the output data of the PLC.

SCON.FAULT must be 0 during the entire sequence.

2 With the rising edge at CPOS.START, the CMAX accepts

the setpoint values, starts the positioning task, sets
SPOS.MC = 0 and acknowledges the starting edge with
SPOS.ACK.